4 CANopen communication settings
4.5 Object directory
30
CANopen for DA1, DC1, DE11
09/16 MN040019EN
www.eaton.com
PowerXL devices support two transmit PDOs (transmit PDO communication
parameters 1800
hex
and 1801
hex
).
Objects 1A00
hex
and 1A01
hex
contain the mapping parameters for the
Tx PDOs.
Index
[hex]
Subindex
[hex]
Objectname
Significance
Access
right
DS
Data type
1800
1801
1st Transmit PDO Parameter
2nd Transmit PDO Parameter
Number of valid subindexes
ro
04
RECORD
00
Number of Entries
Number of entries
ro
03
UNSIGNED8
01
PDO COB-ID
COB-ID of 1st Tx PDO
COB-ID of 2nd Tx PDO
rw
40000180
40000280
+ Node ID
UNSIGNED32
02
Transmission Type
PDO transmission type:
asynchronous
rw
254
UNSIGNED8
03
Inhibit time (100
μ
s)
ro
0
UNSIGNED16
1A00
1st Transmit PDO Mapping
applies for Tx PDO 1
RECORD
00
Number of Mapped Application
Objects
Highest subindex used
rw
4
UNSIGNED8
01
1st Mapping Object
rw
200A0010
UNSIGNED32
02
2nd Mapping Object
rw
200B0010
UNSIGNED32
03
3rd Mapping Object
rw
200D0010
UNSIGNED32
04
4th Mapping Object
rw
200E0010
UNSIGNED32
1A01
2nd Transmit PDO Mapping
applies for Tx PDO 2
RECORD
00
Number of Mapped Application
Objects
Highest subindex used
rw
4
UNSIGNED8
01
1st Mapping Object
rw
200F0010
UNSIGNED32
02
2nd Mapping Object
rw
20100010
UNSIGNED32
03
3rd Mapping Object
rw
20110010
UNSIGNED32
04
4th Mapping Object
rw
200C0010
UNSIGNED32
→
By default, only the first PDO will be enabled.
Summary of Contents for PowerXL DA1