PXL Series Installation
and Operation Manual

Instruction Manual

Page 14 Effective: January 2006

4.5 PXL Premium Display
Calibration Procedure

In some rare cases, the line voltages
displayed on the Premium display may be
incorrect as indicated in the image bellow.
The Auto Calibration feature is what we
actually use in calibrating the Premium
display in the plant. However, this
procedure can be done in the field by
pressing the STEP button before power is
applied to the unit. Then, the operator
selects the system voltage from 208Y to
600Y/D to be displayed.

It measures the input voltage and
assumes that this is equal to the nominal
voltage of the model. So for a 208V
model SPD if the actual input is 230 V,
the display will still be 208V. It measures
and averages a number of cycles then
gets a scaling factor that is used in
displaying 208V in this case.
If this procedure is going to be done in
the field, then calibration must be
performed when the input voltage is close
to nominal to get an accurate display. In
the factory, we set the voltage to 208V
manually through a variac transformer.

4.5.2 Premium Display
Calibration Procedure Steps

!

!
!

!

!

!

!

Shut OFF power to the unit.
Press and hold the STEP button. Do

NOT release (arrow 2)

Apply power to the unit

The display will show:

- first row

- second row

Release the STEP button.

Press the STEP button once to scroll
through the following voltages:

Select Voltage
240V Spt..........240 V Split Phase
240V D/HG......240 V Delta & High Leg
480V Y/D.........480 V Wye/Delta
600V Y/D.........600 V Wye/Delta*
400V Y/D.........400 V Wye/Delta*
220V Y/D.........220 V Wye/Delta*

If the STEP button is pressed again,
selection returns to 208V Wye.

Press TEST (Arrow 7) button once to

accept selected system voltage. Then,
the display will go into Auto-Calibration
and display the system voltage.

Unit is ready to display voltage.

Note: If selection made is incorrect,

repeat all steps starting with STEP 2.

Set Voltage
208 Volts Y

*System Voltages not available for PXL SPD

100KA

VAB VBC VCA

208

208

208

7

2

Effective 01.06

IM 01005001E

information visit: www.eatonelectrical.com

4.5.1 What are the Reasons for
the Auto-Calibration Feature?

!

!
!

To compensate for the differences in

the value of the scaling resistors, offset
voltage of the amplifiers in the display.

To allow for field adjustment if

necessary.

Use of one firmware/hardware for all

voltages. The Premium display board can
display any system voltage from 208 -
600V.

Summary of Contents for Powerware PXL Series

Page 1: ...Installation and Operation Manual for Powerware PXL Series Surge Protective Device IM 01005001E For more information visit www eatonelectrical com Effective 01 06 Instruction Manual IM01005001E...

Page 2: ...Table of contents Description Page Section 1 Introduction 3 Section 2 Installation Procedure 3 Section 3 Operating Features 6 Section 4 Troubleshooting 7 Section 5 Warranty and Technical Assistance 15...

Page 3: ...at hi pot testing not be performed on connected SPDs From the installers point of view it is also important that SPDs are not connected while performing a hi pot test since the SPD will always cause t...

Page 4: ...e Twist and bind together all leads Route the wires such that their overall length is kept to a minimum This reduces line impedance and optimizes performance Strip the ends of the wires and terminate...

Page 5: ...ge 5 Effective January 2006 SPD Figure 3 3 Phase Wye 4 Wire Ground PE Voltage Codes 208Y 480Y CPS Figure 2 3 Phase Delta 3 Wire Ground PE Voltage Codes 240D 480D SPD Figure 1 Single Phase Split Phase...

Page 6: ...perating status each PXL is equipped with status indicator lights All units are equipped with integral fusing Should the SPD fail and create a short circuit the overcurrent will isolate the fault Thes...

Page 7: ...form C relay monitoring contacts by switching the power and back Contact are rated up to 1A 220 VAC NO NC COM OFF ON Note Section 4 Troubleshooting 4 1 Life expectancy Note The PXL is not field repai...

Page 8: ...e surges should not be confused with voltage regulation problems By definition voltage surges occur in the microsecond range and voltage regulation is defined as having a duration of 1 cycle to many c...

Page 9: ...m All LEDs are green No alarms Normal operation 3 phase configuration NA Two green LEDs are ON Split phase configuration Normal operation NA 100KA All green LEDs are ON Alarm disabled LED ON Normal op...

Page 10: ...and N G voltage should be less than 3 volts for 3 phase 4 wire system Lost Neutral Condition 2 Neutral conductor not connected or poor connection intermittent All LEDs are OFF buzzer OFF One or more r...

Page 11: ...formation on the Premium display menu features All LEDs are green No alarms Normal operation 3 phase configuration NA VAN VBN 120 120 Two LEDs are green No alarms Normal operation split phase configur...

Page 12: ...VAC VCA 208 81 208 Lost phase voltage No voltage on specified phase Confirm corresponding SPD phase connection terminals are connected Check breaker voltage Check panel voltage One or more red LEDs ON...

Page 13: ...08 208 208 Internal fuse blown Measure terminal voltage with multimeter and if voltage is in spec then call Press DISABLE ALARM button on display United States support 1 800 809 2772 Australia support...

Page 14: ...5 2 Premium Display Calibration Procedure Steps Shut OFF power to the unit Press and hold the STEP button Do NOT release arrow 2 Apply power to the unit The display will show first row second row Rel...