PXL Series Installation
and Operation Manual
Instruction Manual
Page 13
Effective: January 2006
■
■
■
■
■
■
■
VAB VBC VCA
52
58
50
VAB VBC VCA
180 198
196
Incorrect calibration
Check terminal voltage
with digital multimeter,
Recalibrate only if
measured line voltage is
close to nominal. See
section on calibration.
All green LEDs ON,
Buzzer OFF,
incorrect voltage display.
Incorrect calibration
Check terminal voltage
with digital multimeter,
Check Neutral connection.
All red LEDs ON,
Buzzer ON,
incorrect voltage display.
VAB VBC VCA
208
208
208
Internal fuse blown
Measure terminal voltage with
multimeter and if voltage is in
spec, then call:
Press DISABLE ALARM button
on display.
!
!
!
United States support:
1-800-809-2772
Australia support:
1-300-877-877
South East Asia support:
1-300-322-866
One or more red LEDs ON,
Buzzer ON,
correct voltage display.
Memory lock-up
If pressing the RESET button
does not reset the counters,
Turn OFF the power to the
unit, wait for 5 -10 seconds,
turn ON the unit,
Press the RESET button for
1 - 2 seconds, then release.
One or all counters not
resettable.
Sag
0000
Outage
0000
Table 6. PXL Premium Display (Continued)
PXL Premium Display
Symptom
Cause
Solution
IM 01005001E
information visit: www.eatonelectrical.com
Effective 01.06
■