Lost Neutral
(Condition 1)
Neutral conductor not
connected properly or bad
Neutral
Check Neutral connection
on SPD at lower left hand
side.
Good Neutral?
All red LEDs ON,
incorrect voltage display.
VAB VBC VCA
52
58
50
Lost Neutral
(Condition 2)
Neutral conductor not
connected properly or bad
Neutral
Check Neutral connection
on SPD at lower left hand
side.
Good Neutral?
All LEDs OFF,
buzzer OFF, no voltage
VAB VAC VCA
208
81
208
Lost phase voltage,
No voltage on specified phase.
Confirm corresponding
SPD phase connection
terminals are connected.
Check breaker voltage.
Check panel voltage.
One or more red LEDs ON,
buzzer ON, incorrect voltage
display on affected phase.
Breaker tripped OFF
or no POWER.
All LEDs OFF,
buzzer OFF, blank LCD
display.
Check for proper voltage at
terminals.
Blank LCD display and LED lit.
Unknown - possible warranty
Contact Support:
United States support;
1-800-809-2772
Australia support:
1-300-877-877
South East Asia support;
1-300-322-866
!
!
!
Table 6. PXL Premium Display (Continued)
PXL Premium Display
Symptom
Cause
Solution
Effective 01.06
IM 01005001E