Installation
47
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (650 VA - 1500 VA)
Uncontrolled Copy
UPS with PPDM Startup for 208V-240V Models
To start up the UPS for 208V-240V models:
1.
If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
“UPS Monitoring” on page 54 for instructions.
2.
Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position (see Figure 9 on page 45).
3.
Plug the input power supply cord (use the AS/400 line cord)
into the utility input connector on the PPDM rear panel.
4.
Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance
with national wiring rules.
NOTE
Steps 5 through 8 are for changing the output voltage. The output voltage is
factory-configured for 230V. If you do not need to change the output voltage, skip to
Step 9.
5.
Press the Output
Off button
until the alarm beeps.
All indicators flash simultaneously.
6.
Press and hold the Output On button until the alarm beeps
again.
Two indicators, corresponding with the current setting, remain
flashing. The output voltage is factory-configured for 230V.
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
220V
230V
240V
208V
Figure 10. Output Voltage Indicators
7.
Press the Output
Off button
to scroll through the output
voltage options, top to bottom. Each time you press the button,
the UPS beeps and the next two indicators flash.