CONFIGURATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
36
1
Press and hold the On and Test/Alarm
Reset buttons simultaneously for three
seconds to toggle between Configuration
and Operation modes.
&
4
Press the Test/Alarm Reset
button ONCE to select the
option.
3
Press the On button to
scroll to the next option.
2
On Button
Test/Alarm
Reset Button
Bar Graph Indicators
Figure 21. Using Configuration Mode
Table 4. Configuration Mode LEDs and Options
Bar Graph Indicators
Option
LED Status
Explanation
240V Nominal Output
Voltage
On
Nominal output voltage is 240V.
All other nominal output voltages are disabled.
Flashing
240V is disabled; one of the other output voltage
options is selected.
230V Nominal Output
Voltage
On (default)
Nominal output voltage is 230V.
All other nominal output voltages are disabled.
Flashing
230V is disabled; one of the other output voltage
options is selected.
220V Nominal Output
Voltage
On
Nominal output voltage is 220V.
All other nominal output voltages are disabled.
Flashing
220V is disabled; one of the other output voltage
options is selected.
208V Nominal Output
Voltage
On
Nominal output voltage is 208V.
All other nominal output voltages are disabled.
Flashing
208V is disabled; one of the other output voltage
options is selected.
Site Wiring Fault
Alarm
On
Alarm sounds when the polarity of the outlet is
reversed or the ground connection is missing; have a
qualified electrician repair the outlet wiring.
Flashing
(default)
Alarm DOES NOT sound when the polarity of the outlet
is reversed or the ground connection is missing.