INSTALLATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
24
Load Output Neutral (isolated)
Output
Earthing
Source Input Line 1
Source Input Line 2/N
UPS Output Line 2/N, 230–240V
Input
Earthing
Load Output 115–120V (isolated)
Load Output 230–240V (isolated)
UPS Output Line 1, 230–240V
E4
1
2
3
4
5
6
7
E5
Figure 12. PPDM EURO HW Model Terminal Block
Table 2. PDM Wiring Specifications
Terminal
PDM Wire Function
Terminal Wire
Tightening
Terminal
Position
PPDM HW
PPDM EURO HW
Terminal Wire
Size Rating*
Tightening
Torque
1
Source Input Line 1
Source Input Line 1
2
Source Input Line 2
Source Input Line 2/N
3
Load Output 120V (isolated)
Load Output 230–240V (isolated)
4
Load Output 120V (isolated)
Load Output 115–120V (isolated)
2–17 mm
2
(14–6 AWG)
1.8
±
0.22 Nm
(16
±
2 lb in)
5
Load Output Neutral (isolated)
Load Output Neutral (isolated)
(14–6 AWG)
(16
±
2 lb in)
6
UPS Output Line 1, 208–240V
UPS Output Line 1, 230–240V
7
UPS Output Line 2, 208–240V
UPS Output Line 2/N, 230–240V
E4
Input Ground
Input Earthing
2–5 mm
2
(14–10 AWG)
8 mm
2
2.26
±
0.22 Nm
(20
±
2 lb in)
2.82
±
0.22 Nm
E5
Output Ground
Output Earthing
8 mm
2
(8 AWG)
17 mm
2
(6 AWG)
2.82
±
0.22 Nm
(25
±
2 lb in)
3.95
±
0.22 Nm
(35
±
2 lb in)
* Use 2.0 mm
2
(14 AWG) 75
_
C copper wire minimum.
11.
Replace the wiring access cover and the conduit landing plate.
12.
Plug the input and output cords of the PDM into the input and
output power connectors on the UPS rear panel (see Figure 10).