UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
3-16
Table 3‐6. Input/Output Ratings and External Wiring Requirements for the Two UPM Eaton 9395-825/450, 9395-825/500, and 9395-825/550
– Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
450
410
450
410
500
455
500
455
550
501
550
501
Input and Output Voltage
Volts
400/400
480/480
400/400
480/480
400/400
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
747
600
830
660
913
740
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(4)
500
(5)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps
902
902
1002
1002
1103
1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
–
AWG or kcmil
(each)
4/0
(1)
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Figure 6‐13.
NOTE
Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 825 kVA.