UPS OPERATING INSTRUCTIONS
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
7-18
10.
On the System Status screen, select the
BYPASS
command.
11.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
12.
On the Bypass Control Command screen, select
GO TO BYPASS
.
13.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source, in Bypass mode.
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The
UPM status indicates
SHUTDOWN, CLOSE BATTERY
.
7.3.9
Enable Energy Saver System Mode from the Bypass Command Menu
To enable Energy Saver System mode:
NOTE
The Energy Saver System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
ESS
. The UPM status indicates
ONLINE
. If the battery is not charging, the power
module is off.