
40
9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
Register
number
bit
field
mask
field
set point
name
R/w
format
Value definition
unit
403004
Style1
R
Encoded
0 = false
1 = true
b0 --> LdSel : with long delay protection
b1 --> SdSel : with short delay protection
b2 --> InstSel : with Inst protection
b3 --> GfSel : with ground fault protection
b4 --> ARMSel : with maintenance mode
b5 --> OvrideSel : with override protection
b6 --> RCDSel : with ground fault RCD
b7 --> MotorSel : with motor protection
b8 --> NeuSenorSel : with neutral sensor
b9 --> ThermalSel : with thermal memory
b12 --> VoltSel : with voltage sampling feature
b13 --> ExtADCSel : with external AD7779
403005
3-0
0x000F Style2
R
Encoded
0 = false
1 = true
b0 --> ModbusSel : with integrated Modbus
b1 --> CAMSel : with CAM RS422 port
b2 --> IOModuleSel : with IO module port
b3 --> RelaySel : with relay
b4 --> ZSISel : with ZSI
b12 --> NZM_ACB_Sel
b13 --> IECSel : IEC = 1, UL = 0
403006
8
0x0100 Maintenance
mode: state
R
Encoded
0 = Off 1 = On
0
0x0001 Maintenance
mode: remote
control
R/W
Encoded
0 = Off 1 = On
403007
2-0
0x0007 Arms level
R/W
Encoded
1 = 2.5 * In
2 = 4 * In
3 = 6 * In
4 = 8 * In
5 = 10 * In
A
403008
Frequency
R
Unsigned Range: 50, 60 , 400
Hz
403009
0
0x0001 Rev feed
R/W
Encoded
0 = Forward 1 = Reverse
403010
0
0x0001 Sign convention
R/W
Encoded
sign convention :
0 = IEC, 1 = IEEE, 2 = IEEEalt
403011
Power window
R/W
Encoded
Power demand window :
0 = fixed, 1 = sliding
403012
Power interval
R/W
Encoded
Power demand interval:
[5…60] min
min
403013
Language
R/W
Encoded
set language on local LCD display
0x01 --> English
0x02 --> German
0x03 --> French
0x04 --> Spanish
0x05 --> Italian
0x06 --> Chinese
0x07 --> Russian
0x08 --> Dutch
0x09 --> Danish
0x10 --> Greek
0x11 --> Portuguese
0x12 --> Swedish
0x13 --> Finnish
0x14 --> Czech
0x15 --> Estonian
0x16 --> Hungarian
0x17 --> Lithuanian
0x18 --> Latvian
0x19 --> Polish
0x20 --> Slovenian
0x21 --> Slovak
0x22 --> Bulgarian
0x23 --> Romanian
0x24 --> Croatian
403014
LCD_rotation
R/W
Encoded
Setting LCD display direction
0 <--> horizontal
1 <--> vertical - left
2 <--> vertical - right
403015
Relay_config1
R/W
Encoded
Relay 1/2/3 function configuration
403016
Relay_config2
R/W
Encoded
OFF_RELAY = 0x0000