35
9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
9.2.26 PDG5 PXR25 and 20D settings
frame
800 a
1200 a
1600a iec
800 a
1200/1600a all
all
800
1200
1600
G styles
setting
ir
tr @ 6xir
isd (nxir) tsd(s)
ii (nxin)
ig (nxin) tg (s)
min
320
500
800
0.5
0.5
1.5
0.050
2
2
2
0.20
0.100
max
800
1200
1600
14
24.0
12.0
0.500
18.0
12.0
9.0
1.00
1.000
min
0.067
0.20
0.067
max
0.300
1.00
0.300
step
1.000
1.000
1.000
0.100
0.100
0.010
0.10
0.10
0.10
0.01
0.010
add'l
opt
OFF
Flat
Trip
Flat
I
2
t
Alarm
I2t
9.2.27 PDG6 PXR20 settings
1600 a
2000 a
2500 a
all
1600 a
2000 a
2500 a
all
1600
2000
2500
G styles
setting
ir
tr @ 6xir
isd (nxir)
tsd(s)
ii (nxin)
ig (nxin) tg (s)
switch
1
2
3
4
5
6
7
1
700
1000
1600
0.5
1.5
1.5
1.5
0.050
2
2
2
0.20
0.100
2
800
1100
1700
1.0
2.0
2.0
2.0
0.100
3
3
2.5
0.30
0.150
3
900
1200
1800
2.0
3.0
3.0
2.5
0.150
4
4
3
0.40
0.200
4
1000
1250
1900
4.0
4.0
4.0
3.0
0.200
5
5
3.5
0.60
0.300
5
1100
1400
2000
7.0
5.0
5.0
3.5
0.300
6
6
4
0.80
0.500
6
1200
1600
2100
frame
6.0
6.0
4.0
0.400
7
7
4.5
1.00
0.750
7
1250
1700
2200
12.0
7.0
7.0
4.5
0.500
8
8
5
0.20
1.000
8
1400
1800
2300
15.0
8.0
8.0
5.0
0.067
9
8.5
6
0.50
0.067
9
1500
1900
2400
20.0
9.0
9.0
6.0
0.150
10
9
7
1.00
0.150
10
1600
2000
2500
24.0
OFF
0.300
10.9
8.7
7.0
OFF
0.300
Flat
Trip
Flat
I
2
t
Alarm
I2t
Note that ground fault pickup will not exceed 1200 A
9.2.28 PDG6 PXR25 and 20D settings
frame
1600 a 2000 a 2500 a
all
1600 a
2000 a
2500 a
all
1600
2000
2500
G styles
setting
ir
tr @ 6xir
isd (nxir)
tsd(s)
ii (nxin)
ig (nxin) tg (s)
min
700
1000
1600
0.5
1.5
1.5
1.5
0.050
2
2
2
0.20
0.100
max
1600
2000
2500
24.0
9.0
9.0
6.0
0.500
10.9
8.7
7.0
1.00
1.000
min
0.067
0.20
0.067
max
0.300
1.00
0.300
step
5
5
5
0.100
0.100
0.100
0.100
0.010
0.100
0.100
0.100
0.010
0.010
add'l opt
OFF
Flat
Trip
Flat
I
2
t
Alarm
I2t