38
9 Available protection settings
PXR tRiP units foR PoweR Defense molDeD case ciRcuit bReakeRs
MN012007EN June 2018 www.eaton.com
Register number
Register
address (HeX)
objects
fp
scale
factor
ieee
float
fixed
point (fP)
ieee
float
fixed
point (fP)
Descriptions
units
404877
406413
130C
190C
Maximum VBC
V
10
404879
406415
130E
190E
Minimum VCA
V
10
404881
406417
1310
1910
Maximum VCA
V
10
404883
406419
1312
1912
Minimum VAN
V
10
404885
406421
1314
1914
Maximum VAN
V
10
404887
406423
1316
1916
Minimum VBN
V
10
404889
406425
1318
1918
Maximum VBN
V
10
404891
406427
131A
191A
Minimum VCN
V
10
404893
406429
131C
191C
Maximum VCN
V
10
404959
406495
135E
195E
INST/SDT/HIGH_INST count
1
404961
406497
1360
1960
LDT/GFT count
1
404963
406499
1362
1962
Operations count
1
404965
406501
1364
1964
Short delay trip count
1
404967
406503
1366
1966
Inst delay trip count
1
404969
406505
1368
1968
High current delay trip count
1
404971
406507
136A
196A
Long delay trip count
1
404973
406509
136C
196C
Ground fault trip count
1
404975
406511
136E
196E
Total trip count
1
404977
406513
1370
1970
Test trip count
1
404979
406515
1372
1972
Open by comm count
1
404981
406517
1374
1974
Manual open count
1
404983
406519
1376
1976
Time of last operation (Y,M,D,H,M,S)
1
404995
406531
1382
1982
Max device temperature
C
1
404997
406533
1384
1984
Time of max device temperature
1
405009
406545
1390
1990
Running time: minute
1
405011
406547
1392
1992
Running time: hour
1
405013
406549
1394
1994
Running time: day
1
405015
406551
1396
1996
Life point
1
Energy objects can be obtained in two-register fixed point data format and four-register encoded format, not supporting
in floating point data format.
The two-register format is presented in units of kilowatt hours. The four registers encoded
energy object occupies register 3 through register 0. Register 3 is the high order register
and register 0 is the low order register. Register 3 high byte contains value corresponding
to engineering units(power of 10 signed exponent). Register 3 low byte contains a mantissa
multiplier value(power of 2 exponent). Register 3 through register 0 contains a 48-bit energy
mantissa in units of watthours. The data format of four registers is shown.