Temperature range –20 to 70° C.
Elevation 0-2000M
Humidity 5-95% (non condensing)
POWERXPERT I/O BOARD (PXMIO CARD):
This optional card provides for external discrete IO interfacing
IO1 - 8 Discrete Inputs to external dry contacts
• IO11-IO18 ~ 10mA sink input
• IO19 – 24V internal source for all inputs
IO2 – 2 Solid State relays – external source and load limited to 30VDC and 100mA.
• IO21/IO22 Solid State Output 1 (logic also tied to S1 LED )
•
IO23/IO24 Solid State Output 2
IO3 – 3 Electro mechanical Relays rated for 240VAC/30VDC @ 5Amps
• IO31 R1A - Form A contact Relay1
• IO32 R1C - Common Relay 1
• IO33 R1B - Form B contact Relay 1
• IO34 R2A - Form A contact Relay2
• IO35 R2C - Common Relay 2
• IO36 R2B - Form B contact Relay 2
• IO37 R3A - Form A contact Relay 3
• IO38 R3C - Common Relay 3
• IO39 R3B - Form B contact Relay 3
METER MODULE ELECTRICAL RATINGS
PXPS-1 Standard Power Supply
• Voltage rating100-240VAC, 110-250VDC
•
Maximum Power Rating 50W max,
•
Installation Category CAT III
PXPS-4 Optional Low Voltage Power Supply
• Voltage rating 24-48VDC VDC
•
Maximum Power Rating 50W max,
•
Installation Category CAT III
Metering Circuits
•
CT Current Inputs
• 5A nominal, 20Amp maximum (ANSI class 20)
•
Installation Category CAT III
VT or Vx Voltage Inputs
• 600 V L:L or 347VL:G
•
Installation Category CAT III
DISPLAY MODULE ELECTRICAL RATINGS
DG1 COM0 RS485 communication port to meters, 2K’ max length
• DG11 Data A (-)
• DG12 Data B (+)
• DG13 Shield (RS485 common)
DG2 Display input power 24VDC +/-10%, 6W max draw.
• DG21 Shield
www.eaton.com
IB02601007E
Page 27
3 Mounting and Wiring