3 MOUNTING AND WIRING

WARNING

SHOCK HAZARD: VERIFY THAT ANY INCOMING AC POWER OR FOREIGN POWER 

SOURCES ARE TURNED OFF AND LOCKED OUT BEFORE PERFORMING ANY WORK 

ON THE POWER XPERT 4000/6000/8000 METER OR ASSOCIATED EQUIPMENT. FAIL-

URE TO DO SO CAN RESULT IN INJURY TO PERSONNEL OR DAMAGE TO EQUIP-

MENT.

The Power Xpert Meter 4000/6000/8000 is designed to be installed, operated and main-

tained by adequately trained personnel. These instructions do not include all details, varia-

tions or combinations of the equipment, its storage, delivery, installation, checkout, safe 

operation or maintenance. Compliance with local, state and national regulations, as well 

as with industry standard safety practices for this class of equipment, is imperative. This 

section describes mounting, wiring, startup and miscellaneous details associated with the 

Power Xpert Meter 4000/6000/8000. Every section should be reviewed prior to installing 

this device.

3.1. Mounting the Display Module and Meter Module Separately 

1.  Prepare a cutout in which Display will be placed. The dimensions for this cutout with 

the mounting hole locations are shown in Panel Cutout figure (page 

20)).  There’s a 1:1 

template you can remove from the manual or copy on page 29.

2.  Before cutting the panel, check the required three-dimensional clearances for the Dis-

play case, particularly behind the panel (see the dimension drawing on page meter). 

If mounting on a swinging door, check the swinging clearance of rear projections and 

wired connections. Remember to allow for: extra space for all wiring (including an addi

-

tional 2” for the bending radius (4” for fiber optic), intermediate terminal strips, shorting 

blocks or other required components. Dimensions in Display Module figure on page 

21. 

3.  It is necessary to hold several tolerances when making the cutout and placing the 

holes for the mounting screws. The holes must be located within 1/16” of the drawing 

specifications, and a .188” to 3/16” drill bit is recommended. 

4. 

Place the Display module through the panel cutout. Using the five #8-32X1/2” screws, 

attach the Display to the panel. It is best to attach the top center screw first.

5. 

To mount the Meter Module directly to a flat panel, as recommended, a panel cutout is 

not necessary. There are eight hole locations on the Meter module Mounting Brackets; 

four circular holes and four keyholes. Use either set for mounting. See the Meter Mod-

ule figure on page 

21 for the hole sizes and locations.

3.6. General Instructions

It is recommended that the Power Xpert 4000/6000/8000 Meter be mounted in an electri-

cal switchgear enclosure that is suitable for its environment. The Power Xpert Display and 

Meter Modules are generally mounted separately (see manual for mounting together).  

While it is recommended that the Display Module be door or panel mounted, the Meter 

Module can be mounted remotely from the Display Module on a flat surface or panel else

-

where in the enclosure.

• 

The Meter Module must remain vertical at all times to maintain proper ventilation.

• 

The Display and Meter Modules may be installed in a Pollution Degree II environment.

• 

If the Meter Module is mounted remotely, the Display Module MUST be connected to 

earth ground.

• 

The Meter Module should be protected from accidental contact with live terminals in 

the enclosure.  A 1/8 inch steel panel or door, solidly grounded, is recommended.

www.eaton.com

 

IB02601007E

 

Page 19

 

3 Mounting and Wiring

Summary of Contents for Power Xpert Meter 4000

Page 1: ...www eaton com Power Xpert Meter 4000 6000 8000 Quick Start Guide Instruction Leaflet IB02601007E Effective January 2012...

Page 2: ...nd or Eaton Corpora tion s Eaton experience and judgment and may not cover all contin gencies If further information is required an Eaton sales office should be consulted Sale of the product shown in...

Page 3: ...ule 13 Programming the Meter Module using the Embedded Web Server Interface 14 Programming the Meter Module via the Optional Communications Expansion Card 15 3 Mounting and Wiring 19 Mounting the Disp...

Page 4: ......

Page 5: ...e attempting to install or operate the equipment Improper wiring could cause death injury and or equipment damage Only qualified personnel are to service the Power Xpert Meter TROUBLESHOOTING PROCEDUR...

Page 6: ...Page 6 IB02601007E www eaton com 1 Introduction...

Page 7: ...PROXIMITY TO EXPOSED ENERGIZED LIVE ELECTRICAL WIRING AND OR PARTS WHERE THE HAZARD OF FATAL ELECTRIC SHOCK IS PRESENT Exercise extreme care to avoid injury or death Always disconnect lock out and ta...

Page 8: ...or Vdc Fabricate a power cord of suitable length and connect to the power supply via the Power Supply Connection shown in Figure 1 Note The Green Health LED should blink at a slow rate once per secon...

Page 9: ...ire Y Up to Up to 600 V L L 347 L N 3 phase 4 Wire Y Above Up to 600 V L L 347 L N See Installation for wiring diagrams DS 1 DS 2 DS 3 OFF OFF ON is Normal OFF is Safe Mode No restrictions user ID Pas...

Page 10: ...Line 1 or Va VTV2 Line 2 or Vb VTV3 Line 3 or Vc VTV4 Line 4 or Vn neutral VTVR Metering Reference Ground VX Optional Auxiliary Voltage Connections VXV6 Line 1 or Va2 VXV7 Line 2 or Vb2 VXV8 Line 3 or...

Page 11: ...Specifications Table for wiring Display PXCM Description Terminal Cable Terminal DA DG1 1 TP CM5 1 DB DG1 2 TP CM5 2 SH DG1 3 SDW CM5 3 TP Twisted Pair SDW Shield Drain Wire B Connect CM6 Figure 5 lo...

Page 12: ...414 449 7100 E185559 MEASURING EQUIPMENT 20NL Catalog PXD MMG Serial XXXXXX Style 66D2117G01 Power Supply 24 VDC 20 SELV 8W MAX MADE IN USA Date Code WYYYYMMDD Rev XXX Oper Temp 20 TO 60 C MAC Address...

Page 13: ...clockwise and counterclockwise to select highlight options on the screen Once highlighted push dial to get more information about the topic Back Button Push to return to the previous selection Display...

Page 14: ...to be 192 168 1 1 C Set the laptop s IP address to 192 168 1 100 by completing the following steps Click Window s Start Then click Settings Control Panel Windows 2000 or Control Panel Windows XP Vist...

Page 15: ...the factory at time of manufacture If the card is installed as an after sale option follow instructions for physical installation that accom pany the card or refer to the manual To set up the card fol...

Page 16: ...ome Page will be displayed If DHCP is enabled the user must find the IP address via the Local Configuration port Setup Diagnostics Communication Ethernet or Local Display 2 On the Meter Webserver home...

Page 17: ...The Optional Communications Expansion CE card also provides communication via Modbus RTU CE3 CE4 see manual for Modbus instructions The RS485 CE3 port supports Modbus RTU slave to a master monitoring...

Page 18: ...Page 18 IB02601007E www eaton com 2 Quick Start Guide for the Meter Module...

Page 19: ...for fiber optic intermediate terminal strips shorting blocks or other required components Dimensions in Display Module figure on page 21 3 It is necessary to hold several tolerances when making the cu...

Page 20: ...s attached The Display Module comes standard with the required hardware five 8 32 x 50 LG Phillips Pan Int SEMS Screws for mounting the unit to a door or panel Panel Cutout Dimensions for Display Modu...

Page 21: ...l support 1 800 809 2772 or 1 414 449 7100 www eaton com electrical Customer Satisfaction http www eaton com pxm 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED THIS DEVICE COMPLIES WITH PART 15 O...

Page 22: ...T VX Larger wire will not connect properly to the terminal block Wiring diagrams contacts are shown in their de energized position Because the Power Xpert Meter monitors the neutral to ground voltage...

Page 23: ...www eaton com IB02601007E Page 23 3 Mounting and Wiring...

Page 24: ...A BUSS type KTK R 1 2 Fast Acting or equivalent fuses are recommended for the Power Xpert Meter VT connections External fuses should be installed in the potential transformer lines as specified in the...

Page 25: ...ew the RS485 wiring spec for wiring specifications Tie the communication cable shield to ground only once at the RS485 master device Cable Specifications Terminal Port Name Port Type Port Connection C...

Page 26: ...at one location only Data line definition As per the RS485 standard In an idle marked state logic 1 Data B will be electrically than Data A Note When connecting to third party RS485 devices their data...

Page 27: ...Relay 2 IO36 R2B Form B contact Relay 2 IO37 R3A Form A contact Relay 3 IO38 R3C Common Relay 3 IO39 R3B Form B contact Relay 3 METER MODULE ELECTRICAL RATINGS PXPS 1 Standard Power Supply Voltage rat...

Page 28: ...G INSTRUCTIONS If the meter or display modules require cleaning the power and metering inputs should be turned off through their disconnects The meter and display should be cleaned with a dry clean cl...

Page 29: ...7 32 185 9 3 66 93 0 3 00 76 2 3 00 76 2 7 76 197 1 7 32 185 9 2 00 50 8 4 00 101 6 0 22 5 6 R0 06 R1 5 0 19 4 8 5x inches mm 3 15 Display Unit Mounting Template...

Page 30: ...poration Electrical Sector 1111 Superior Ave Cleveland OH 44114 United States 877 ETN CARE 877 386 2273 Eaton com 2012 Eaton Corporation All Rights Reserved Printed in USA Publication No IB02601007E J...

Reviews: