Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
27
C
Chhaapptteerr 66 TTrroouubblleesshhoooottiinngg IInnssttaallllaattiioonn P
Prroobblleem
mss
The following troubleshooting tips cover the most common installation and setup problems.
If problems continue after performing the following checks, contact Eaton Service, see paragraph
66..11
C
Coom
mm
muunniiccaattiioonn P
Prroobblleem
mss
The most common JCOMM and BCMS installation and setup problems are communications problems.
66..11..11
C
Chheecckk M
Mooddbbuuss N
Neettw
woorrkk S
Seettuupp ffoorr tthhee B
BC
CM
MS
S B
Booaarrdd
•
Verify that ModBus connectors have the correct pin-out. (See paragraph
)
•
4-wire Modbus is the default network configuration. If using 2-wire Modbus, check that Modbus
connectors on the Connections Panel are jumpered TX+ to RX+ and TX- to RX-. (See paragraph
66..11..22
C
Chheecckk M
Mooddbbuuss A
Addddrreesssseess
Modbus addresses can only be set using BCMSII setup software. Modbus addresses are not stored in the
points lists.
Verify that the Modbus addresses have been setup correctly in the BCMS board:
•
If a JCOMM WaveStar Color Monitor is installed as a local power monitoring station:
–
Check the monitor’s front panel to verify that there are no communication errors present.
–
Verify that each panelboard can be displayed on the monitor.
–
Access the monitor setup page by accessing the setup pressing the ESC key and verify that the
upstream addresses of the monitor are set correctly:
○
The WaveStar Color Monitor remaps its downstream devices to upstream addresses that can be
accessed by the BMS. The number of devices monitored by the monitor is shown on its setup
page.
○
For example, if the WaveStar display monitors four panelboards in a JCOMM and the panelboard
addresses are 1, 2, 3, and 4. If the monitor’s address is 20, it will respond to addresses 21, 22, 23,
24 for panelboard addresses, when addressed by the BMS. (See paragraph
Remapping Modbus Addresses with Monitors
•
Verify that the BMS is addressing the correct addresses. A very common problem is that the BMS
addresses the
downstream
addresses that were established in setup when a monitor or WaveStar BCMS
Hub is present. The BMS should be addressing the addresses
upstream
of the monitor or Hub, as they
have been remapped. (See paragraph
Modbus Addressing with Monitor Installed
•
If the display does not resume communication with the BMS, verify that its upstream cable is undamaged
and that communication wires are correctly connected.
66..22
B
BC
CM
MS
S B
Booaarrdd P
Poow
weerr P
Prroobblleem
mss
•
Check the LED’s on the BCMS board. LEDs should be blinking when the BCMS board has 24VDC power.
•
If power LEDs are not blinking, check the connections from the 24VDC power supply (on the right side
Power Panel) through the terminal blocks to the BCMS board. (See
)
Summary of Contents for PDI JCOMM
Page 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Page 4: ......
Page 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Page 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Page 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Page 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Page 50: ...P 16400110701 P 164001107 01...