Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
23
C
Chhaapptteerr 55 N
Neettw
woorrkkiinngg
This chapter describes incorporation of JCOMMs and their BCMSs into a network. Networking problems are
among the most common BCMS installation problems. Network addressing in particular should be carefully
planned.
55..11
M
Mooddbbuuss N
Neettw
woorrkk S
Seettuupp
The networking protocol for JCOMM BCMS boards is Modbus RTU with the following characteristics:
•
9600 bps network speed
•
Even (default), odd, or no parity (specified during BCMS software setup)
•
4-wire or 2-wire (2-wire selected by jumpers on the Connection Panel)
All customer Modbus network connections are made through two Modbus connectors on the Connections
Panel (
). The customer provides Modbus cables for network connections.
Figure 14. Modbus Connections
All JCOMMs in a Modbus loop must be configured identically. 4-wire Modbus is the default. With a JCOMM
monitor, 4-wire Modbus must be used downstream of the monitor.
2-wire Modbus can be used on JCOMM network connections when a monitor is not installed. For 2-wire
Modbus loops, install jumpers connecting RX- to TX- and RX+ to TX+ on each JCOMM Modbus connector.
Summary of Contents for PDI JCOMM
Page 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Page 4: ......
Page 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Page 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Page 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Page 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Page 50: ...P 16400110701 P 164001107 01...