Chapter 4 — Commissioning
Fieldbus Board Parameters
The RS-485 Communication Board (OPTCB) is commissioned with the control keypad by
giving values to appropriate parameters in the Expander board menu M4.
Expander Board Menu (M4)
The Expander board menu makes it possible for the user (1) to see what expander boards are
connected to the control board, and (2) to view and edit the parameters associated with the
expander board.
Enter the following menu level
(
G4
)
with the menu button
(right arrow). At this level, you
can browse through slots A to E with the Browser buttons to see which expander boards are
installed. On the bottom line of the display, you also see the number of parameter groups
associated with the board.
If you press the menu button
again, you will reach the parameter group level where there
are two groups: Editable parameters and Monitored values. Another press on the menu
button
takes you to either of these groups.
Siemens FLN Communication Parameters
To commission the Siemens FLN Communication Board, enter the level P4.5.1.# from the
Expander Board Menu 4. The board can be installed in either slot D (G4.4) or slot E (G4.5). It is
installed in slot E from the factory.
Table 4-1: Changing the FLN Board Commissioning Parameter Values
The SLAVE ADDRESS of every device must be set before connecting to the bus. The SLAVE
ADDRESS must be the same as in the master configuration. The baud rate is automatically
configured for 4800. No adjustment is possible.
1. Review the following drive and fieldbus application parameter settings:
●
Check that application HVX9.11 or later is selected.
Application Selection S3.2 = HVX9.11 or later version
Refer to the
HVX9000 User Manual
for instructions on how to set parameters using
the keypad.
●
Check that start source auto is set to network. This allows the user to provide start/
stop commands from the FLN network.
Parameter P1.1.17 = Fieldbus
●
Check that reference source auto is set to network. This allows the user to provide
a speed reference from the FLN network.
Parameter P1.1.18 = Fieldbus
●
Check that the HOA mode is set to AUTO.
#
Name
Default
Range
Description
1
Communication
Timeout
10
0 – OFF
1 – 300 s
See
Communication Timeout
on
Page 4-2.