Group 30 — Inputs
5-24
MVX9000 User Manual
Descriptions of
Parameter Settings
Settings 29, 30
A digital input may be used to shut the output off (pause) and not display a fault.
This is different from settings 19 and 20 because they produce a “bb” display.
Figure 5-30: Digital Input Terminal Settings 29, 30
Settings 31, 32
A digital input is used to select the AUTO mode (setting 31) or HAND mode
(setting 32) during HAND/OFF/AUTO (HOA).
Figure 5-31: Digital Input Terminal Settings 31, 32
Setting 33
A digital input is used to select the LOCAL control when in LOCAL/REMOTE
mode.
Figure 5-32: Digital Input Terminal Setting 33
29, 30:Output
S
hut-Off
RO3 RO2 RO1
DI1 DI2 DI3 DI4 DI5 DI6 COM AO+ AI1 +10V AI2
DO1 DOC
COM
32:Ha
n
d Co
n
trol Locatio
n
31:Auto Co
n
trol Locatio
n
RO3 RO2 RO1
DI1 DI2 DI3 DI4 DI5 DI6 COM AO+ AI1 +10V AI2
DO1 DOC
COM
33:Local/Remote
RO3 RO2 RO1
DI1 DI2 DI3 DI4 DI5 DI6 COM AO+ AI1 +10V AI2
DO1 DOC
COM