Group 30 — Inputs
5-22
MVX9000 User Manual
Descriptions of
Parameter Settings
Settings 22, 23
Setting 22 allows an input terminal to enable the AC drive’s internal PLC program
and Setting 23 allows an input terminal to pause the PLC program.
Figure 5-25: Digital Input Terminal Settings 22, 23
Setting 24
A digital input terminal may be used to increase the AC drive’s internal counter.
When an input is received, the counter is increased by 1. The counter input may
be connected to an external Pulse Signal Generator to count a process or unit of
material. See the diagram below.
Figure 5-26: Digital Input Terminal Setting 24
23:Pause PLC
22:Run PLC
RO3 RO2 RO1
DI1 DI2 DI3 DI4 DI5 DI6 COM AO+ AI1
DOC
COM
AI2
DO1
+10V
24:Counter input
RO3 RO2 RO1
DI1 DI2 DI3 DI4 DI5 DI6 COM AO+ AI1 +10V AI2
DO1 DOC
COM
2 ms
2 ms
Indication value
(trigger enable)
Counter trigger signal
Multi-function input terminal
Signal output with 30.17
counter value is attained.
(30.17=3)
(40.03/40.04 or 40.06/40.07)
Signal output with 30.16
counter value is attained.
(30.16=5)
The trigger timing
can't be less than
2 ms.(<250 Hz)
(40.03/40.04 or 40.06/40.07)
C0 C1
C2
C3
C4
C5
C1 C2
Summary of Contents for MVX9000 Series
Page 2: ......
Page 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Page 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Page 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Page 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Page 179: ......