MVX9000 Parameter Listing
B-2
MVX9000 User Manual
Parameter T
ables
MVX9000 Parameter Listing
Table B-1: 20 — BASIC GROUPING (Quick Start)
Modbus Groups Page #
Description
Range
Default
User
Settings
0000H
20.01
50.05
5-5
Motor Nameplate
Frequency
10.0 to 400.0 Hz
60.0
0001H
20.02
50.06
5-5
Motor Nameplate
Voltage
115/230V drives: 1.0 to 255V
230
460V drives: 1.0 to 510V
460
575V drives: 1.0 to 637V
575
0002H
20.03
50.01
5-5
Source of Master
Frequency
00: Master frequency
determined by digital keypad
up/down
01
01: Master frequency
determined by keypad
potentiometer
02: Master frequency
determined by 0 to +10V
input on AI terminal
03: Master frequency
determined by 4 to 20 mA
input on AI terminal
04: Master frequency
determined by RS-485
communication interface
0003H
20.04
50.02
5-5
Source of Operation
command
00: Operation commands
determined by digital keypad
00
01: Operation commands
determined by external
control terminals, keypad
STOP is effective
02: Operation commands
determined by external
control terminals, keypad
STOP is ineffective
03: Operation commands
determined by RS-485
interface, keypad STOP is
effective
04: Operation commands
determined by RS-485
interface, keypad STOP is
ineffective
0004H
20.05
60.01
5-6
Motor Rated Current
30 to 120%
FLA
0005H
20.06
50.09
5-6
Minimum Output
Frequency
0.0 to 20.0 Hz
1.5
0006H
20.07
50.04
5-6
Maximum Output
Frequency
50.0 to 400.0 Hz
60.0
0007H
20.08
50.12
5-6
Acceleration Time 1
0.01 to 600.0 sec
10.0
0008H
20.09
50.13
5-6
Deceleration Time 1
0.01 to 600.0 sec
10.0
Summary of Contents for MVX9000 Series
Page 2: ......
Page 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Page 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Page 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Page 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Page 179: ......