6.2 Digital output (DO)
The DO mode enables an open-collector or contact switch output on the safe side to
control an on/off device in the field.
Figure 6.2
- Digital output options
The MTL4-BSIS module base can be fitted with a shorting link (LK1 – see diagram) to
enable the user to increase the output current for solenoid drivers, if required. Consult
the datasheet for the individual parameters.
MTL4-LNKIS-50
IS power jumper link (Pk50)
WARNING!
Fitting link LK1 will change the Safety Description of the product. Refer to
the certificate for details.
Note:
LFD, when configured, is provided by detecting the field conditions using a 24V
1mS pulse every 1 second. Some LED and sounders may respond to this pulse when
enabled.
6.3 Digital output (DO - with switched contacts)
This configuration is an option when relay contacts are required to drive a digital load in
the field. Choose one of the Relay module bases from the table below to suit the field
wiring.
Figure 6.3
- Digital output with relay options
MTL4-SD
Loop
Disconnect
LK1
A
B
C
V out
Input/
Output
Common
MTL4-ADIO
MTL4-BSIS
1
10V 14mA
2
Input/Output
3
Common
4
26.5V 90/136mA
Contact
output
FIELD
+
Solenoid
Valve
–
SYSTEM
Output -
V
Power +
Voltage
output
Digital
output
MTL4-SD
Loop
Disconnect
A
B
C
Power +
MTL4-ADIO
MTL4-BSxxR
1
NO
X
X
X
2
NC
3
Com
Contact
output
Voltage
output
Open
collector
+
IS Contact
Control
–
V
Output –
FIELD
SYSTEM