Accuracy:
Free running ± 1 min./mo.
@ 25°C (77°F). Automati
-
cally updated by PowerNet
host.
IPONI Communications
(Section 10 contains more protocols.)
Type:
2 wire, 115.2 kHz carrier
Baud Rate:
1,200 ASK or 9,600 FSK
Maximum Distance:
10,000 feet
Protocol:
INCOM
Functions:
Read/write set points
Read metered values
Read trip/alarms
Read events
Read history
Reset history
Reset functions
Emergency override
Trip
View starting profile
Logging
Log Book:
100 events
Log Event:
20 trips and alarms
Log Start:
Last 4 starts
Start Profile:
Last 4 starts (communications
port only)
History Records:
Motor, trips, alarms, and totals
Environmental Ratings
Operating Temperature:
-20° to +60°C (-4° to +140°F)
Storage Temperature:
-45° to +85°C (-49° to +185°F)
Humidity:
0 to 95% non-condensing
Dimensions (fixed Mount Case Only)
Height:
10.25 in. (26.04 cm)
Width:
6.72 in. (17.0 cm)
Depth:
4.3 in. (10.9 cm)
Weight:
4.0 lbs. (1.8 kg)
7.0 lbs. (3.2 kg) (with URTD
and PONI)
Standards
ANSI/IEEE C37.90-1989
Standard for Relay Systems Associated with Electric Power Apparatus.
ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
ANSI/IEEE C37.90.2-1995
Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
UL-1053
Ground Fault Sensing and Relaying Equipment
Emissions (EN-50081-2):
EN 50011 CISPR-11, Class A, CFR 47 FCC Part 15
Subpart b Class A
EN-61000-6-2
Immunity
EN 61000-4-2
ESD
EN 61000-4-3
RF Radiated Immunity
EN 61000-4-4
EFT/Burst Immunity
EN 61000-4-5
Surge Immunity
EN 61000-4-6
RF Conducted Immunity
EN 61000-4-8
Power Frequency Magnetic Field Immunity
EN 61000-4-11
Voltage Variation Immunity
Summary of Contents for MP-3000
Page 1: ...IM02602002E www eaton com IM02602002E Rev E MP 3000 Motor Protection Relay ...
Page 18: ...IM02602002E Page 4 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 32: ...IM02602002E Page 4 20 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 54: ...IM02602002E Page 6 10 www eaton com MP 3000 Figure 6 7 Typical AC Supply and URTD Wiring ...
Page 55: ...IM02602002E www eaton com Page 6 11 MP 3000 Figure 6 8 Alternatives for Discrete Input Wiring ...
Page 60: ...IM02602002E Page 7 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 71: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 1 Rotor Temperature Tracking ...
Page 72: ...IM02602002E Page 9 www eaton com MP 3000 Figure 9 2 Motor Protection Curve ...
Page 73: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 3 Underload Jam Protection Curve ...
Page 76: ...IM02602002E Page 9 12 www eaton com MP 3000 Figure 9 6 Motor Start and Run Cycles ...
Page 79: ...IM02602002E www eaton com Page 10 MP 3000 Figure 10 1 PONI Communications Module ...
Page 90: ...IM02602002E Page 12 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 99: ...www eaton com MP 3000 IIM02602002E This Page Intentionally Left Blank Page 13 9 ...