IM02602002E
Page
4-14
www.eaton.com
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
VALUE SELECTED
PaGE 12, SP SyS SETTINGS fOR SySTEM CONfIGURaTION
1
TP MODE X
CONFIGURE TRIP RELAY OUTPUT TO
BE MODE 1 --
TRIP RELAY ENERGIZES ON TRIP
EVENT OR MODE 2 --TRIP RELAY
ENERGIZES ON POWER UP AND
DE-ENERGIZES ON TRIP EVENT
Toggles between TP MODE 1 and
TP MODE2
2
AL MODE X
CONFIGURE ALARM RELAY OUTPUT
TO BE MODE 1 - ALARM RELAY
ENERGIZES ON ALARM EVENT OR
MODE 2 - ALARM RELAY ENERGIZES
ON POWER UP AND DE-ENERGIZES
ON ALARM EVENT
Toggles between AL MODE1 and
aL MODE2
3
AX1 MOD X
CONFIGURE AUX1 RELAY OUTPUT TO
BE MODE 1 - AUX1 RELAY ENERGIZES
ON AUX1 EVENT OR MODE 2 - AUX1
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX1 EVENT
Toggles between
aX1 MOD1
and AX1 MOD2
4
AX2 MOD X
CONFIGURE AUX2 RELAY OUTPUT TO
BE MODE 1 - AUX2 RELAY ENERGIZES
ON AUX2 EVENT OR MODE 2 - AUX2
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX2 EVENT
Toggles between
aX2 MOD1
and AX2 MOD2
5
MAN I2T
or
AUTO I2T
AUTO OR MANUAL I2T RESET
Toggles between
MaN I2T
and AUTO I2T
6
RUN PGM
or
STOP PGM
ENABLE UNIT TO BE PROGRAMMED
WHILE MOTOR IS RUNNING
Toggles between RUN PGM and
STOP PGM
7
EMRG EN
or
EMRG DIS
EMERGENCY OVERRIDE ENABLE
EMRG EN - ENABLE EMERGENCY
OVERRIDE
EMRG DIS - DISABLE EMERGENCY
OVERRIDE
Toggles between EMRG EN and
EMRG DIS
8
12 HOUR
or
24 HOUR
SET MONITOR MODE CLOCK DISPLAY
12 HOUR - AM/PM TIME DISPLAYED
24 HOUR - 24 HOUR TIME DISPLAYED
Toggles between
12 hOUR
and 24 HOUR
9
M D Y
D M Y
SET REAL TIME DATE DISPLAY -
MONTH DAY YEAR OR
DAY MONTH YEAR
M D y
or D M Y
10
IQ2 DIS
INCOM COMMUNICATIONS MODE
Toggles between
DIS
and EN
IQ2 EN -IQ1000II EMULATION
IQ2 DIS - MP3000 COMMUNICATION
11
RLYF TRP
RLYF ALM
or
RLYF T+A
INTERNAL DIAGNOSTIC FAILURE
ACTIVATES TRIP AND OR ALARM
RELAY
Toggles between RLYF TRP, RLYF ALM and
RLyf T+a
12
INCT DIS
or
INCT EN
INCOM TRIP DISABLED OR ENABLED
Toggles between INCT DIS and
INCT EN
13
DISARMED
or
ARMED
ARM OR DISARM TRIP RELAY
WARNING DISARM WILL NOT ALLOW
TRIP RELAY TO FUNCTION
Toggles between
aRMED
and DISARMED
PaGE 13, SP TEST SETTINGS fOR TESTING INPUTS aND OUTPUTS*
1
3 PHASE
or
1 PHASE
SINGLE PHASE TEST MODE OR
THREE PHASE PROTECTION MODE
Toggles between
3-PhaSE
and 1-PHASE
NOTE: 1-PHASE is for bench testing ONLY.
2
TRP ENER
or
TRP DENR
TRP ENER - ENERGIZE TRIP RELAY
TRP DENR - DE-ENERGIZE TRIP RELAY
Toggles between TRP ENER and TRP DENR
Press and hold
Reset
button to perform
selected test
(none)
3
ALM ENER
or
ALM DENR
ALM ENER - ENERGIZE ALARM RELAY
ALM DENR - DE-ENERGIZE ALARM
RELAY
Toggles between ALM ENER AND ALM DENR
Press and hold
Reset
button to perform
selected test
(none)
Summary of Contents for MP-3000
Page 1: ...IM02602002E www eaton com IM02602002E Rev E MP 3000 Motor Protection Relay ...
Page 18: ...IM02602002E Page 4 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 32: ...IM02602002E Page 4 20 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 54: ...IM02602002E Page 6 10 www eaton com MP 3000 Figure 6 7 Typical AC Supply and URTD Wiring ...
Page 55: ...IM02602002E www eaton com Page 6 11 MP 3000 Figure 6 8 Alternatives for Discrete Input Wiring ...
Page 60: ...IM02602002E Page 7 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 71: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 1 Rotor Temperature Tracking ...
Page 72: ...IM02602002E Page 9 www eaton com MP 3000 Figure 9 2 Motor Protection Curve ...
Page 73: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 3 Underload Jam Protection Curve ...
Page 76: ...IM02602002E Page 9 12 www eaton com MP 3000 Figure 9 6 Motor Start and Run Cycles ...
Page 79: ...IM02602002E www eaton com Page 10 MP 3000 Figure 10 1 PONI Communications Module ...
Page 90: ...IM02602002E Page 12 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 99: ...www eaton com MP 3000 IIM02602002E This Page Intentionally Left Blank Page 13 9 ...