Turn off ac power again. Troubleshoot the discrete input
and/or URTD wiring, if necessary.
Reinstall the power plug into J3 of the URTD.
Check the URTD configuration DIP switches, to insure they
are set for the types of RTDs actually installed in the motor
and load equipment. See URTD I.L. 17367 for specifics.
Reconnect the leads disconnected from terminals 8 and 10
Turn on ac power again.
Recheck P13L7, the state of discrete input 1, if used. It
should report DI 1 ON.
Recheck P13L8, the state of discrete input 2, if used. It
should report DI 2 ON.
Turn off ac power again. Troubleshoot the discrete input
wiring.
Remove the jumpers on the remote contacts or set them to
the normal state.
Use the MP-3000 discrete input test page indications to test
the actual operation of the contacts, if possible.
7.4 further Checking of the Relay with aC Power
Apply ac power to the relay and optional URTD.
The MP-3000 quickly initializes and displays its status, usu
-
ally READY—3, unless the relay sample has been subjected
to an unusual combination of settings and recent prior
service or testing. Usually, one or more output relays can be
heard to click as they are energized.
The Protection LED on the faceplate should light.
If the URTD is connected, press the Monitor mode button
and navigate to the MONT RTD page. If the MONT RTD
page cannot be accessed, the URTD module is dead or not
communicating with the relay at all. Troubleshoot the com
-
munications wiring or optical fiber and URTD power.
Check the 11 temperature display lines. Each connected
RTD should display an appropriate value (e.g. 25 at room
temperature). Non-functioning or unused RTD inputs display
a — character for a value.
7.5 Checking Data Communications
If the relay is equipped with a PONI, check it to confirm that
the communications network is connected.
Visit the PowerNet or other host and check the monitoring
displays for the particular MP-3000.
Confirm that the displays in view are for the correct relay.
This is easily done by disconnecting and reconnecting the
network connector.
If communications can not be established, check for address
conflicts on the network (multiple devices set to the same
address) or incorrect setting of the address switches on the
PONI.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
1.
2.
3.
4.
5.
1.
2.
3.
4.
7.6 Entering Relay Settings
Make a copy of Table 4.3 as a worksheet for recording set-
ting choices.
Read Sections 5 and 9 carefully for guidance in selecting
settings.
If desired, PowerNet or PowerPort data communications
can be used to download a preconfigured setting record to
the relay from a disk file or from a convenient worksheet on
the host display. IMPACC cannot be used to enter settings
to an MP-3000.
If electronic communications are not used, enter the settings
through the front panel in Program mode, using the Prog
button behind the security door.
After settings have been entered, exit the program mode by
pressing the Program button again.
Verify that the settings have been correctly entered using
the View SP mode button.
Reconfirm that the motor nameplate values agree with the
corresponding relay settings.
Reconfirm that the ratios of the phase and ground CTs in the
gear agree with the PCT and GCT settings of the relay.
CaUTION
ThE MP-3000 haS MORE ThaN 100 SETTINGS, WhICh aRE
EaSy TO CONfUSE. DO NOT aTTEMPT TO ENTER VaLUES
WIThOUT USING ThE aPPROPRIaTE SET POINT RECORD
ShEET. IMPROPER OPERaTION aND/OR PERSONaL INjURy
COULD RESULT If ThIS PROCEDURE IS NOT fOLLOWED.
7.7 Checking Contact Outputs
DaNGER
BE aWaRE Of WhEThER CONTROL POWER IS aPPLIED TO
ThE OUTPUT CONTaCTS BEfORE TESTING. aVOID
unex-
pecteD
OPERaTION Of ThE MOTOR CONTaCTOR OR OThER
CONTROLLED DEVICES DURING TESTING. PERSONaL INjURy
OR DaMaGE COULD RESULT.
Determine the mode of each of the output relays. Look at
settings P12L1 through P12L4.
If possible and safe, use a live test of the actual wiring or
devices operated by the MP-3000 output contacts to verify
contact operation and check wiring.
A voltmeter can be used to check energized contacts. Use
an ohmmeter or continuity checker
only
on dead, discon-
nected circuits.
With MP-3000 power applied, each output relay set for
Mode 1 should have its NO contact open and its NC contact
closed.
Each relay set for Mode 2 should have its NO contact
closed and its NC contact open.
Enter the Program mode. Navigate to Page 13, SP TEST.
Settings P13L2 to P13 L5 can be used to set up each of the
output relays for test.
1.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
4.
5.
6.
Summary of Contents for MP-3000
Page 1: ...IM02602002E www eaton com IM02602002E Rev E MP 3000 Motor Protection Relay ...
Page 18: ...IM02602002E Page 4 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 32: ...IM02602002E Page 4 20 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 54: ...IM02602002E Page 6 10 www eaton com MP 3000 Figure 6 7 Typical AC Supply and URTD Wiring ...
Page 55: ...IM02602002E www eaton com Page 6 11 MP 3000 Figure 6 8 Alternatives for Discrete Input Wiring ...
Page 60: ...IM02602002E Page 7 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 71: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 1 Rotor Temperature Tracking ...
Page 72: ...IM02602002E Page 9 www eaton com MP 3000 Figure 9 2 Motor Protection Curve ...
Page 73: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 3 Underload Jam Protection Curve ...
Page 76: ...IM02602002E Page 9 12 www eaton com MP 3000 Figure 9 6 Motor Start and Run Cycles ...
Page 79: ...IM02602002E www eaton com Page 10 MP 3000 Figure 10 1 PONI Communications Module ...
Page 90: ...IM02602002E Page 12 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 99: ...www eaton com MP 3000 IIM02602002E This Page Intentionally Left Blank Page 13 9 ...