12
Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01
44..22
C
Coonnnneecctt O
Ouuttppuutt P
Poow
weerr C
Caabblleess
The Mini PDU has (20) output receptacles ((16) x 30A, (4) x 20A) in the rear of the unit, numbered to correspond
to front panelboard circuit breakers.
Figure 7. Mini PDU Output Receptacles
Receptacles
1 - 16 (30A):
16 x L6-30R
2-Pole/3W Grounding
Receptacles
17 - 20 (20A):
4 x L5-20R 1-Pole/2W
Grounding
Rear Output Receptacles
Front Panel Circuit Breakers
A customer output cable kit (MOD67210) is provided with the Mini PDU with the following cables:
•
(8) x 20 ft. 30A SOOW 8/3C AWG, 90°C, 600VAC, Flex with Hubble connectors HBL2621/HBL2623
•
(8) x 50 ft. 30A SOOW 8/3C AWG, 90°C, 600VAC, Flex with Hubble connectors HBL2621/HBL2623
•
(4) x 20 ft. 20A SOOW 8/3C AWG, 90°C, 600VAC, Flex with Hubble connectors HBL2311/HBL2313
Cables are intended to be plugged into server power receptacles on one end and to the Mini PDU back panel
receptacles on the other end.
Cable servers to the Mini PDU:
NOTE
Work from top to bottom.