Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01

General operating conditions for transformer operation are according to IEEE C57.12.01 (most recent
edition).

Relative humidity range: 0% to 95% non-condensing.

Maximum altitude 10,000 ft. The PDU is de-rated above 10,000 ft. For operations at heights above 3,300
ft., please contact the factory before ordering.

If the PDU is not to be immediately installed and energized, it should be carefully stored in a warm, dry
environment, preferably a heated building with air circulation and a uniform temperature to prevent
condensation. It is especially important that the transformer be free of condensation and protected from
contamination. The transformer and PDU should be stored in their factory protective coverings.

Storage temperature range must be within these extremes: -30

C to +70

C (-22

F to 158

F).

If the transformer has been exposed to moisture, it should be dried out before being energized. Consult Eaton
Service if the unit has been exposed to moisture or contamination.

11..44

U

Ussiinngg TThhiiss M

Maannuuaall

Read this manual thoroughly and make sure you understand the procedures before you attempt to install, set
up, operate or carry out any maintenance work on this Eaton product.

Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
unit being installed or operated.

11..55

C

Coonnvveennttiioonnss U

Usseedd iinn TThhiiss M

Maannuuaall

This manual uses these type conventions:

NOTE

Some conventions only apply to display screens (if installed).

Bold type

highlights important concepts in discussions, key terms in procedures, and menu options, or

represents a command or option that you type or enter at a prompt.

Italic type

highlights notes and new terms where they are defined.

Screen type

represents information that appears on the screen or LCD.

Icon

Description

Information notes call attention to important features or instructions.

[Keys]

Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].

11..66

S

Syym

mbboollss,, C

Coonnttrroollss,, aanndd IInnddiiccaattoorrss

The following are examples of symbols used on the UPS or accessories to alert you to important information:

Special Symbols

The following are examples of symbols used on the UPS or accessories to alert you to important
information:

RISK OF ELECTRIC SHOCK

 - Observe the warning associated with the risk of

electric shock symbol.

CAUTION:  REFER TO OPERATOR'S MANUAL

 - Refer to your operator's manual for

additional information, such as important operating and maintenance
instructions.

This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead‐acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.

Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
Phillips and Pozidriv are registered trademarks of Phillips Screw Company.

E

Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be

reproduced in any way without the express written approval of Eaton Corporation.

RISK OF ELECTRIC SHOCK

- Observe the warning associated with the risk of electric shock symbol.

Special Symbols

The following are examples of symbols used on the UPS or accessories to alert you to important
information:

RISK OF ELECTRIC SHOCK

 - Observe the warning associated with the risk of

electric shock symbol.

CAUTION:  REFER TO OPERATOR'S MANUAL

 - Refer to your operator's manual for

additional information, such as important operating and maintenance
instructions.

This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead‐acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.

Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
Phillips and Pozidriv are registered trademarks of Phillips Screw Company.

E

Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be

reproduced in any way without the express written approval of Eaton Corporation.

CAUTION: REFER TO OPERATOR'S MANUAL

- Refer to your operator's manual for additional

information, such as important operating and maintenance instructions.

Introduction

Summary of Contents for Mini PDU

Page 1: ...p n 164001117 Revision 01 Installation and Operation Manual Eaton 30 kVA Mini Power Distribution Unit...

Page 2: ...ontains important instructions that you should follow during installation and maintenance of the UPS Please read all instructions before operating the equipment and save this manual for future referen...

Page 3: ...m a host of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton 9395 Uninterruptible Power Supply system wi...

Page 4: ...e license to use the Firmware in conjunction with the operation of the product to which the Firmware pertains or other products as described by Eaton in the Documentation Licensee does not acquire any...

Page 5: ...CT IS AT LICENSEE S SOLE RISK 5 0 GENERAL PROVISIONS 5 1 Update Policy Eaton may from time to time but has no obligation to create Updates of the Firmware or components thereof 5 2 Limitation on Liabi...

Page 6: ...nctions Programs Pages Programs aspx or to any national of any such country wherever located who intends to transmit or transport the Firmware back to such country ii to any end user who Licensee know...

Page 7: ...nfidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton Accordingly Eaton will be entitled to preliminary and permanent injunctive and oth...

Page 8: ......

Page 9: ...7 7 3 1 Bill of Materials 7 3 2 Receiving and Unpacking the Mini PDU 7 3 3 Required Clearances 7 3 4 Moving and Placing the Mini PDU 8 3 5 Attaching the Cable Ladder 8 4 4 P Po ow we er r C Ca ab bll...

Page 10: ...x Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Table of Contents...

Page 11: ...Figure 2 Seismic Brace 8 Figure 3 Mini PDU to Cable Ladder Bracket Attachment Points 9 Figure 4 Cable Ladder Attachment 10 Figure 5 Mini PDU Input Cable Receptacle 11 Figure 6 Input Cable Receptacle...

Page 12: ...xii Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 List of Figures...

Page 13: ...A Mini PDU 1 1 2 2 D De es sc cr riip pt tiio on n Table 1 Dimensions and Weight Dimensions 48 H x 16 W x 42 D Casters and Leveling feet add 0 1 5 H Weight Approx 850 lbs Table 2 Circuit Breakers Spec...

Page 14: ...highlights notes and new terms where they are defined Screen type represents information that appears on the screen or LCD Icon Description Information notes call attention to important features or in...

Page 15: ...icates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local r...

Page 16: ...4 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Introduction...

Page 17: ...Disconnect and lock out all power supplying equipment before working on or installing components Use a properly rated voltage sensing device to confirm power is OFF Leave ample space for attaching an...

Page 18: ...6 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Safety...

Page 19: ...t and before removing packaging inspect the packaging for visible damage If damage is evident notify the shipping company and Eaton see 1 7 Getting Help File any damage claims with the shipping compan...

Page 20: ...ver racks and withdraw the forklift Unit has casters and can be precisely rolled into position Seismic brace must face opposite the server rack 4 Adjust leveling feet to stabilize the unit using an op...

Page 21: ...Install the Cable Ladder over the Cable Ladder Bracket as shown below Screws to secure the Cable Ladder to its Bracket are stored in the 4 PEM nuts of the Bracket Specification Screw 3 8 16 X 75 lg H...

Page 22: ...the Bracket s PEM nuts Aluminum Cable Ladder 12 W x 4 D x 72 H Part Number MIS68130 A licensed electrician must install the Mini PDU and connect external cables and wiring Installers should use Lock O...

Page 23: ...ry Brush Panel Input Cable Receptacle Cable Ladder 4 4 1 1 C Co on nn ne ec ct t I In np pu ut t P Po ow we er r C Ca ab blle e The Mini PDU has an input cable connected to the main input circuit brea...

Page 24: ...L5 20R 1 Pole 2W Grounding Rear Output Receptacles Front Panel Circuit Breakers A customer output cable kit MOD67210 is provided with the Mini PDU with the following cables 8 x 20 ft 30A SOOW 8 3C AW...

Page 25: ...p row of receptacles first then each lower row successively 2 Select an appropriate cable for the server and connect it to server input power 3 Run the cable down the Cable Ladder securing it to the C...

Page 26: ...14 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Power Cabling...

Page 27: ...t has a rear locking door to access output receptacles Side panels lift off Figure 9 Mini PDU Locking Doors Front Doors Rear Door Lexan Door Dead Front Door 5 5 2 2 C Co on nt tr ro olls s The only co...

Page 28: ...Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Figure 10 Mini PDU Circuit Breakers Main Input Circuit Breaker Subfeed Secondary Circuit Breaker Panelboard Circuit Bre...

Page 29: ...ns for remedial actions proactive replacements and upgrades 6 6 3 3 E Ea at to on n P Pr ro ov viid de es s F Flle ex xiib biilliit ty y a an nd d C Co om mm miit tm me en nt t We understand that serv...

Page 30: ...18 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Eaton Service Contracts...

Page 31: ...n 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 19 C Ch ha ap pt te er r 7 7 A Ap pp pe en nd diix x 3 30 0 k kV VA A M Miin nii P PD DU U D Dr ra aw wiin ng g...

Page 32: ...20 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Appendix 30 kVA Mini PDU Drawings...

Page 33: ...Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 21 Appendix 30 kVA Mini PDU Drawings...

Page 34: ...22 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Appendix 30 kVA Mini PDU Drawings...

Page 35: ...Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 23 Appendix 30 kVA Mini PDU Drawings...

Page 36: ...16400111701 164001117 01...

Reviews: