Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01

11

C

Chhaapptteerr 44 P

Poow

weerr C

Caabblliinngg

The Mini PDU does not require wiring at the customer site. Input and output power cables plug in to
receptacles in the unit.

Run both input and output cables down the cable ladder, securing cables to the ladder.

Figure 5. Mini PDU Input Cable Receptacle

Output Cable Entry 

Brush Panel

Input Cable 

Receptacle

Cable Ladder

44..11

C

Coonnnneecctt IInnppuutt P

Poow

weerr C

Caabbllee

The Mini PDU has an input cable connected to the main input circuit breaker. (For shipping, the input cable may
be partially inserted into the Output Cable Entry tray. )

The input power cable extends eight feet from the top of the unit with this receptacle:

Hubbel CS8165C, twist-lock, 50A, 3-pole, 4-wire, 480V male.

Figure 6. Input Cable Receptacle

Customer must supply a grounded input power cable with matching female connector.

Connect the customer input power cable to the input power receptacle and lock.

Summary of Contents for Mini PDU

Page 1: ...p n 164001117 Revision 01 Installation and Operation Manual Eaton 30 kVA Mini Power Distribution Unit...

Page 2: ...ontains important instructions that you should follow during installation and maintenance of the UPS Please read all instructions before operating the equipment and save this manual for future referen...

Page 3: ...m a host of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton 9395 Uninterruptible Power Supply system wi...

Page 4: ...e license to use the Firmware in conjunction with the operation of the product to which the Firmware pertains or other products as described by Eaton in the Documentation Licensee does not acquire any...

Page 5: ...CT IS AT LICENSEE S SOLE RISK 5 0 GENERAL PROVISIONS 5 1 Update Policy Eaton may from time to time but has no obligation to create Updates of the Firmware or components thereof 5 2 Limitation on Liabi...

Page 6: ...nctions Programs Pages Programs aspx or to any national of any such country wherever located who intends to transmit or transport the Firmware back to such country ii to any end user who Licensee know...

Page 7: ...nfidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton Accordingly Eaton will be entitled to preliminary and permanent injunctive and oth...

Page 8: ......

Page 9: ...7 7 3 1 Bill of Materials 7 3 2 Receiving and Unpacking the Mini PDU 7 3 3 Required Clearances 7 3 4 Moving and Placing the Mini PDU 8 3 5 Attaching the Cable Ladder 8 4 4 P Po ow we er r C Ca ab bll...

Page 10: ...x Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Table of Contents...

Page 11: ...Figure 2 Seismic Brace 8 Figure 3 Mini PDU to Cable Ladder Bracket Attachment Points 9 Figure 4 Cable Ladder Attachment 10 Figure 5 Mini PDU Input Cable Receptacle 11 Figure 6 Input Cable Receptacle...

Page 12: ...xii Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 List of Figures...

Page 13: ...A Mini PDU 1 1 2 2 D De es sc cr riip pt tiio on n Table 1 Dimensions and Weight Dimensions 48 H x 16 W x 42 D Casters and Leveling feet add 0 1 5 H Weight Approx 850 lbs Table 2 Circuit Breakers Spec...

Page 14: ...highlights notes and new terms where they are defined Screen type represents information that appears on the screen or LCD Icon Description Information notes call attention to important features or in...

Page 15: ...icates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local r...

Page 16: ...4 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Introduction...

Page 17: ...Disconnect and lock out all power supplying equipment before working on or installing components Use a properly rated voltage sensing device to confirm power is OFF Leave ample space for attaching an...

Page 18: ...6 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Safety...

Page 19: ...t and before removing packaging inspect the packaging for visible damage If damage is evident notify the shipping company and Eaton see 1 7 Getting Help File any damage claims with the shipping compan...

Page 20: ...ver racks and withdraw the forklift Unit has casters and can be precisely rolled into position Seismic brace must face opposite the server rack 4 Adjust leveling feet to stabilize the unit using an op...

Page 21: ...Install the Cable Ladder over the Cable Ladder Bracket as shown below Screws to secure the Cable Ladder to its Bracket are stored in the 4 PEM nuts of the Bracket Specification Screw 3 8 16 X 75 lg H...

Page 22: ...the Bracket s PEM nuts Aluminum Cable Ladder 12 W x 4 D x 72 H Part Number MIS68130 A licensed electrician must install the Mini PDU and connect external cables and wiring Installers should use Lock O...

Page 23: ...ry Brush Panel Input Cable Receptacle Cable Ladder 4 4 1 1 C Co on nn ne ec ct t I In np pu ut t P Po ow we er r C Ca ab blle e The Mini PDU has an input cable connected to the main input circuit brea...

Page 24: ...L5 20R 1 Pole 2W Grounding Rear Output Receptacles Front Panel Circuit Breakers A customer output cable kit MOD67210 is provided with the Mini PDU with the following cables 8 x 20 ft 30A SOOW 8 3C AW...

Page 25: ...p row of receptacles first then each lower row successively 2 Select an appropriate cable for the server and connect it to server input power 3 Run the cable down the Cable Ladder securing it to the C...

Page 26: ...14 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Power Cabling...

Page 27: ...t has a rear locking door to access output receptacles Side panels lift off Figure 9 Mini PDU Locking Doors Front Doors Rear Door Lexan Door Dead Front Door 5 5 2 2 C Co on nt tr ro olls s The only co...

Page 28: ...Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Figure 10 Mini PDU Circuit Breakers Main Input Circuit Breaker Subfeed Secondary Circuit Breaker Panelboard Circuit Bre...

Page 29: ...ns for remedial actions proactive replacements and upgrades 6 6 3 3 E Ea at to on n P Pr ro ov viid de es s F Flle ex xiib biilliit ty y a an nd d C Co om mm miit tm me en nt t We understand that serv...

Page 30: ...18 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Eaton Service Contracts...

Page 31: ...n 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 19 C Ch ha ap pt te er r 7 7 A Ap pp pe en nd diix x 3 30 0 k kV VA A M Miin nii P PD DU U D Dr ra aw wiin ng g...

Page 32: ...20 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Appendix 30 kVA Mini PDU Drawings...

Page 33: ...Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 21 Appendix 30 kVA Mini PDU Drawings...

Page 34: ...22 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Appendix 30 kVA Mini PDU Drawings...

Page 35: ...Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 23 Appendix 30 kVA Mini PDU Drawings...

Page 36: ...16400111701 164001117 01...

Reviews: