Settings
Contextual help of the web interface – 86
•
•
•
•
•
Main administrator password never expire
Lock account
Lock account after a number of invalid tries
Main administrator account will never block
Account timeout
To set the session expiration rules, apply the following restrictions:
No activity timeout (in minutes).
If there is no activity, session expires after the specified amount of time.
Session lease time (in minutes).
If there is activity, session still expires after the specified amount of time.
3.7.2.2 Default settings and possible parameters - Global user settings and Local
users
Default setting
Possible parameters
Password settings
Minimum length — enabled (8)
Minimum upper case — enabled (1)
Minimum lower case — enabled (1)
Minimum digit — enabled (1)
Special character — enabled (1)
Minimum length — enable (6-32)/disable
Minimum upper case — enable (0-32)/disable
Minimum lower case — enable (0-32)/disable
Minimum digit — enable (0-32)/disable
Special character — enable (0-32)/disable
Password expiration
Number of days until password expires — disabled
Main administrator password never expires — disabled
Number of days until password expires — disable/
enable (1-99999)
Main administrator password never expires — disable/
enable
Lock account
Lock account after xx invalid tries — disabled
Main administrator account never blocks — disabled
Lock account after xx invalid tries — disable/enable
(1-99)
Main administrator account never blocks — disable/
enable
Account timeout
No activity timeout — 60 minutes
Session lease time — 120 minutes
No activity timeout — 1-60 minutes
Session lease time — 60-720 minutes
1.
2.
Main administrator password never expires
If this feature is disabled, the administrator account can be locked after the password expiration.
If Enabled, the administrator password never expires, make sure it is changed regularly.
1.
2.
Main administrator account will never block
If this feature is disabled, the administrator account can be locked after the number of failed connections
defined.
If Enabled, the security level of the administrator account is reduced because unlimited password entry
attempts are allowed.
Summary of Contents for INDGW-X2
Page 1: ...UPS Industrial Gateway Card INDGW X2 User s Guide English 10 18 2021 2 2 3 ...
Page 23: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 24: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 27 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 28 ...
Page 35: ...Home Contextual help of the web interface 37 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 37: ...Home Contextual help of the web interface 39 3 2 7 2 2 Bypass mode 3 2 7 2 3 Battery mode ...
Page 61: ...Protection Contextual help of the web interface 63 Example 4 Custom ...
Page 62: ...Protection Contextual help of the web interface 64 Settings 1 Settings 2 ...
Page 218: ...Default settings and possible parameters Information 220 ...
Page 266: ...Acronyms and abbreviations Information 268 ...
Page 273: ......