3.5.1.5 Troubleshooting
Card wrong timestamp leads to "Full acquisition has failed" error message on Software
Symptoms:
IPP/IPM shows the error message "The full data acquisition has failed" even if the credentials are correct.
Possible cause:
The Network module timestamp is not correct.
Probably the MQTT certificate is not valid at Network module date.
Action:
Set
the
right
date,
time
and
timezone.
If
possible,
use
a
NTP
server,
refer
to
help>>>Settings>>>General>>>System details>>>Time & date settings