Protection
Contextual help of the web interface – 64
•
•
•
Shutdown criteria are set per power source (outlet groups) if they are present in the UPS.
3.5.4.1.1 Shutdown criteria selection
The available criteria for shutdown are listed below:
a Maximize availability (default)
To end the shutdown sequence 30s before the end of backup time.
b Immediate OFF
To initiate the shutdown sequence when on battery for 10 seconds.
c Custom
Several conditions can be set to define shutdown criteria:
To initiate the shutdown sequence when on battery for 10 seconds.
To initiate the sequence when the battery reaches the set capacity in (%)
To initiate or end the shutdown sequence after the set time in (s) before the end of backup time.
When there are several conditions to start the shutdown sequence, the shutdown sequence will start as soon as one of the
condition is reached.
d Settings examples
All the following examples are using below agent's settings.
→
Shutdown time: 210s
Example 1: Maximize availability
By default, shutdown criterias are set to Maximize availability.
When primary shuts OFF, both group1 and group 2 shut OFF immediately.
So if Primary is set to Immediate OFF, groups policies should be restricted to Immediate OFF.
Summary of Contents for INDGW-M2
Page 1: ...UPS Industrial Gateway Card INDGW M2 User s Guide English 06 25 2021 2 1 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 63: ...Protection Contextual help of the web interface 63 3 5 4 1 Shutdown on power outage criteria ...
Page 65: ...Protection Contextual help of the web interface 65 Example 2 Immediate OFF ...
Page 66: ...Protection Contextual help of the web interface 66 Example 4 Custom Settings 1 ...
Page 268: ...Acronyms and abbreviations Information 268 ...
Page 276: ......