Figure 23. DC Power Terminal Detail – Eaton 93PM IBC-LH (480V)
TRAY 10
Ground Terminals
IBC DC (+) Output
to UPS Positive
Terminal (+)
IBC DC (-) Output
to UPS Negative
Terminal (-)
44..33..22
S
Sttaannddaalloonnee P
Poow
weerr W
Wiirriinngg
NOTE 1
Standalone IBC installations with three or four IBCs require a customer supplied external
tie point and circuit breaker or disconnect between the IBCs and the UPS.
NOTE 2
Up to four IBCs can be installed in a standalone configuration.
Use this procedure to wire standalone 93PM Integrated Battery Cabinets to the 93PM UPS cabinet.
To install wiring to connections:
1.
Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton
93PM UPS Installation and Operation manual, listed in paragraph
, for UPS
operating procedures.
2.
Open the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open.