Before initial operation, any foreign matter shall be removed from the 
apparatus.

Apparatus without a protective cap may only be built into approved 
or certified enclosures, operating panels or switch cabinets.

The national safety rules and regulations for the prevention of 
accidents, as well as the safety instructions included in these 
operating instructions, that, like this text, are set in italics, shall be 
observed!

3   Conformity with standards

The apparatus is conform to the standards specified in the EU-Declaration 
of conformity, enclosed separately.

References to standards and directives in these operating instructions 
always relate to the latest version. Other additions (e.g. details relating to 
the year) shall be observed.

Field of application

The control units are intended for use in potentially explosive atmospheres 
in zones 1,2 in accordance with IEC/EN 60079-10-1.

The enclosure materials used, including any external metal parts, are high 
quality materials that ensure a corrosion resistance and resistance to 
chemical substances according to the requirements for use in a ”normal 
industrial atmosphere”: 
 

- impact resistant polyamide 

When used in extremely aggressive atmospheres, the additional data 
relating to the chemical resistance of the plastics being used shall be 
taken from the data sheet  
GHG 902 4001 P0001.

Application / Properties

The control units GHG 418 .. are intended for the local control of electrical 
installations in potentially explosive atmospheres. These apparatus 
components are built into switch cabinets, operating panels or machinery 
according to the individual requirements.

X

ATEX - IEC

For this purpose, they must be installed in suitable Ex-e enclosures 

when used in explosive atmospheres.

X

ATEX - IEC

The installation of the actuator GHG41 in equipment of 2G and M2 

must be tested and certified separately. At this, the thermal parameters 
have to be verified among others.

X

ATEX - IEC

 The creepage and clearance distance have to be fulfil the  

EN/IEC 60079-7, table 1.

The version with gold-tipped contacts is suited for switching extra-low 
voltage circuits.  Special attention shall be paid to the maximum current 
load (see technical data, page 6). The contact chamber of the gold-tipped 
version is  marked with the letter ”G” or colour-coded.

To ensure a safe and reliable disconnection, the normally closed contacts 
are designed as compulsory opening contacts. 

Where required, the bases are fitted with 0.6 W resistors, fine-wire fuses and 
diodes (max. power dissipation 1 W).

When the switch collar of small control switches is cut out at the 
respective locking position, they can be padlocked  
(padlock shackle Ø up to 5 mm).

X

ATEX - IEC

 The installation of the signal lamp GHG417 1805 in equipment of 2G 

must be tested and certified separately. At this, the thermal parameters 
have to be verified among others.

Apparatus versions without a protective cap are only issued with a 
”Component Certificate” and may only be used if built into certified 
Ex-e protective enclosures.

The apparatus versions with a protective cap are fully certified and can, 
therefore, be operated directly.

Any admissibly high mechanical stress of the protective cap that 
might impair the explosion protection shall be avoided.

The data according to sections 3 and 4 shall be taken into account 
during use.

Applications other than those described are not permissible without 
a written  declaration of consent from Messrs. COOPER CROUSE-
HINDS / CEAG.

During operation the instructions stated in section 7 of the operating 
instructions shall be observed.

The sole responsibility with respect to the suitability and proper use 
of the control switches with regard to the basic requirements of 
these instructions (see technical data) lies with the operator.

6 Installation

The relevant national regulations(e.g. Betr.Si.V, the equipment safety law 
for Germany) and the generally recognized rules of engineering apply for 
the installation and operation (IEC/EN 600079-14).

The improper installation and operation of control switches may 
result in the invalidation of the guarantee.

6.1  Mounting / Dismantling

Components for panel mounting are mounted in accordance with Figs. 1 
– 4, page13 and according to the following:

1

.  The operating and indicating element, item 4, is inserted from the 

front into the bore hole ( Ø 30.3 mm) of the switch panel or enclosure, 
maximum wall thickness 5 mm. 
Here special attention shall be paid to the correct fit of the seal, item 
5, and of the element (positioning lug on element shall fit into the 
recess, see dimensions drawing on page 12.)

2

.  Tighten the counter-nut, item 3, using the mounting tool, item 12 

(Accessory Order No. GHG4101914R0001).

Excessive tightening can result in damage to the actuator elements.

3.

  The Ex-d components, item 1, can be completed by adding a 

protective cap, item 7, an optional item – see section 5 –to form fully 
certified built-in apparatus.

 The minimum distances of the operating elements have to be 

observed (see Dimension drawing page).

The partially certified built-in components can be retrofitted with the 
protective cap Pos. 7, optionally as described under point 5, can be 
completed to fully certified built-in devices. 

To do this, the contact protection of the terminals must first be removed.

The protective cap is mounted as follows:

4.

  Remove the pressure screw with seal, item 8, from the protective 

cap, item 7, and adapt the sealing rings  to suit the cable cross 
section.

5.

  Push the cable, item 9, through the pressure screw with cable seal, 

item 8, of the seal, item 6, and the protective cap, item 7.

6.

  Connect the cable. Fix the strain-relief, item 1, with the screws, item 

11, to the cable and engage in the guide grooves, items 15a and 15b, 
of the component, item 1 (see Fig. 3).

Explosion-protected control units GHG 418

GB

Summary of Contents for GHG 418 Series

Page 1: ...ingua della Comunit Europea potete richiederla al vostro rappresentante Cooper Crouse Hinds CEAG LT ios naudojimo instrukcijos i verstos J su gimt j kalb galite pareikalauti atsakingoje Cooper Crouse...

Page 2: ...ometer 9 2 Principles 10 2 1 Safety instructions 10 3 Conformity with standards 10 4 Field of application 10 5 Application Properties 10 6 Installation 11 6 1 Mounting 11 6 2 Opening apparatus Electri...

Page 3: ...Nm EU Baumusterpr fbescheinigung IBExU14ATEX1030U Ger tekennzeichnung nach 2014 34 EU und der Normenreihe EN 60079 II 2 G Ex db eb IIC IIB IIB H2 Gb I M 2 Ex db eb I Mb IECEx Konformit tsbescheinigung...

Page 4: ...0 mm starr Pr fdrehmoment Anschlussklemmen 2 5 Nm Gewicht ca 0 15 kg 1 3 Signallampe GHG 418 1806 1 4 Potentiometer GHG 418 16 R Explosionsgesch tzte Steuerger te GHG 418 D 2 Legende Achtung Dieses Sy...

Page 5: ...1805 in Betriebsmittel der Kategorie 2G muss gesondert gepr ft und best tigt werden Dabei sind unter anderem die thermische Parameter zu berpr fen Die Betriebstem peratur darf 68 C nicht bersteigen D...

Page 6: ...rehen siehe Punkt 6 3 Die Demontage erfolgt in umgekehrter Reihenfolge Um die Schutzkappe wieder zu l sen werden mit dem Demontagewerkzeug Pos 13 die Rastfl gel wie in Bild 4 dargestellt aus der Nut d...

Page 7: ...EU Type Examination Certificate IBExU14ATEX1030U Marking acc to 2014 34 EU and standard of series EN 60079 II 2 G Ex db eb IIC IIB IIB H2 Gb I M 2 Ex db eb I Mb IECEx type examination certificate IEC...

Page 8: ...i Datas U i 30 V I i 100 mA Ci 0 Li 0 Pi 750 mW Supply terminal 2 x 1 0 2 5 mm 1 x 4 0 mm single wire Test torques 2 5 Nm Weight approx 0 15 kg 1 3 Signal lamp GHG 418 1806R 2 Principles Caution This...

Page 9: ...t this the thermal parameters have to be verified among others Apparatus versions without a protective cap are only issued with a Component Certificate and may only be used if built into certified Ex...

Page 10: ...e tests specified in the individual national regulations shall be performed In addition to this before being put into operation the correct functioning and installation of the apparatus and built in c...

Page 11: ...Nm Vis auto taraudeuse d charge 2 00 Nm 1 2 Bouton poussoir et interrupteur GHG 418 11 R Attestation d examen CE de type IBExU14ATEX1030U Marquage selon 2014 34 UE et directive EN 60079 0 II 2 G Ex d...

Page 12: ...Le groupe d explosion et la classe de temp rature marqu s sur les appareils devront tre respect s Il n est pas permis de transformer ou de modifier les boites de commande Seuls des boites de commande...

Page 13: ...ives F Avant la premi re mise en service tout corps tranger doit tre t de la boite de commande Des unit s sans capot protecteur ne doivent tre install es que dans des enveloppes des tableaux ou des ar...

Page 14: ...s cela peut tre nuisible l indice de protection 6 5 Mise en service Avant la mise en service de l appareil les v rifications sp cifi es dans les r glements nationaux individuels devront tre ex cut es...

Page 15: ...e coup de poing Schlagtaster NOT AUS Schl sseltaster mit Schl sselentriegelung Mushroom head pushbutton Key operated EMERG STOP pushbutton with key release Bouton poussoir coup de poing Bouton poussoi...

Page 16: ...000 49 2017 MS Eaton is a registered trademark All trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved s...

Reviews: