16.3 Emergency stop monitoring/manual, monitored start
A1
13
23
33
41
A2
S3 4
1 4
2 4
3 4
4 2
( )
ESR5-...
K1
K1
K2
S2
M
(N )
24-230V AC /DC
K2
K1
K2
M
S3 5
( )
L
S
S
11
13
(+)
( )
S2 2
( )
S
S
2 1
10
(GND)
( )
S1 2
( )
S1
•
Two-channel emergency stop monitoring
•
Manual, monitored start
•
Monitoring of external, force-guided contactors
•
Suitable up to category 4, PL e (EN ISO 13849-1), SIL 3 (EN 62061), if
cross-circuits in the control to the actuator can be ruled out
Figure 16:
Emergency stop monitoring/manual, monitored start
Key:
Cross-circuits in the cable installation can be excluded if the
safety relay and external contactors K1 and K2 are located in the
same electrical installation space.
S1
Emergency stop button
S2
Manual reset device
K1/K2
Force-guided contactors