6
Manual ESR5-NO-31-UC
07/2017 MN049014 EN www.eaton.com
3 Technical data
Hardware/firmware version
HW/FW
> 00/--
The technical data and safety characteristics are valid as of the specified HW/FW version.
Input data
Rated control circuit supply voltage U
S
24 V AC/DC ... 230 V AC/DC -15 % / +10 %
Rated control supply current I
S
typ. 103 mA (24 V DC)
typ. 47 mA (48 V DC)
typ. 38 mA (110 V AC)
typ. 21 mA (230 V AC)
Input voltage range "0" signal
0 V DC ... 5 V DC (for safe Off; to S10/S12/S13)
Input current range "0" signal
0 mA ... 2 mA (for safe Off; to S10/S12/S13)
Inrush current
< 80 A (
Δ
t = 50
μ
s at Us)
< 5 mA (at Us/Ix to S10/S12/S13)
> -5 mA (at Us/Ix to S22)
< 10 mA (at Us/Ix to S34/S35)
Current consumption
< 5 mA (at Us/Ix to S10/S12/S13/S34/S35)
> -5 mA (at Us/Ix to S22)
Power consumption at U
S
2,7 W (at DC)
2,9 W (at AC)
Apparent power
typ. 5 VA (at U
S
)
Voltage at input/start and feedback circuit
24 V DC -20 % / +25 %
Filter time
2 ms (at A1 in the event of voltage dips at Us)
max. 1,5 ms (to S10-S12; test pulse width; at 24 V DC)
7,5 ms (to S10-S12; test pulse rate; at 24 V DC)
test pulse rate = 5 x test pulse width
Max. permissible overall conductor resistance
(Input and reset circuit at U
S
)
150
Ω
Typical response time at Us
< 100 ms (manual, monitored start)
< 150 ms (automatic start)
Typical starting time at Us
< 200 ms (at controlled via A1)
Typical release time at Us
< 20 ms (at controlled via sensor circuit)
Recovery time
< 500 ms
Restart time
< 1 s
Maximum switching frequency
1 Hz
Concurrence input 1/2
∞
Operating voltage display
1 x green LED
Status display
3 x green LED
Protective circuit
U
S
:
surge protection 275 V varistor / 411 V suppressor diode
Inputs: protection against polarity reversal, surge protection
38.6 V suppressor diode
Summary of Contents for ESR5-NO-31-UC
Page 4: ...2...