Troubleshooting
Eaton ePDU G3 Troubleshooting Guide P-164000278—Rev 1
www.eaton.com/ePDU
18
2
207400
ePDU Temperature Critical High Threshold
The temperature level reading is greater than the
value configured as the high temperature critical
threshold.
2
211000
Eaton ePDU Input 1 Current No Threshold
No section current threshold has been triggered.
2
211100
Eaton ePDU Input 1 Low Current Warning
The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2
211200
Eaton ePDU Input 1 Low Current Critical
The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2
211300
Eaton ePDU Input 1 Over Current Warning
The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2
211400
Eaton ePDU Input 1 Over Current Critical
The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2
212000
Eaton ePDU Input 1 Voltage No Threshold
No section voltage threshold has been triggered.
2
212100
Eaton ePDU Input 1 Low Voltage Warning
The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2
212200
Eaton ePDU Input 1 Low Voltage Critical
The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2
212300
Eaton ePDU Input 1 Over Voltage Warning
The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2
212400
Eaton ePDU Input 1 Over Voltage Critical
The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2
213000
Eaton ePDU Input 1 Frequency OK
Utility frequency is within the +/- 3 Hz of Nominal
frequency.
2
213100
Eaton ePDU Input 1 Frequency Out of Range
Utility frequency greater or less than +/- 3 Hz of
Nominal frequency.
2
214000
Eaton ePDU Input 2 Current No Threshold
No section current threshold has been triggered.
2
214100
Eaton ePDU Input 2 Low Current Warning
The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2
214200
Eaton ePDU Input 2 Low Current Critical
The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2
214300
Eaton ePDU Input 2 High Current Warning
The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2
214400
Eaton ePDU Input 2 High Current Critical
The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2
215000
Eaton ePDU Input 2 Voltage No Threshold
No section voltage threshold has been triggered.
2
215100
Eaton ePDU Input 2 Low Voltage Warning
The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
Table 11. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code
Alarm or Event
Description