3 Commissioning
3.1 Exchange of modules
Electronic motor starter EMS-...-SWD
12/18 MN034002ZU-DE/EN
www.eaton.com
59
3 Commissioning
After the U
AUX
SmartWire-DT supply voltage is switched on, the
Ready
,
ERR
,
L
, and
R
LEDs (in the case of EMS-ROS-…-SWD) or the
Ready
,
ERR
,
and
ON
LEDs (in the case of EMS-DOS-…-SWD) will all light up once as part
of an LED test. After this, the
Ready
LED will light up with a continuous
green light.
After the U
SWD
SmartWire-DT supply voltage is switched on, the green
SmartWire-DT diagnostic LED (
Ready
) will flash with a frequency of 1 Hz to
indicate that the electronic motor starter is ready for commissioning. During
commissioning, the gateway will automatically assign addresses to all the
modules on the SmartWire-DT line (when the configuration button on the
gateway is pressed). The diagnostic LED will flash during this address
assignment process. Once the address assignment process is complete, the
diagnostic LED will light up with a continuous light.
3.1 Exchange of modules
Whenever you replace a module, you will need to press the configuration
button after replacing the module and switching on the voltage. When this is
done, the new module will be assigned an address.
DANGER
The entire SmartWire-DT system must be switched off before
replacing the electronic motor starter.
NOTICE
The order of the SmartWire-DT units must not be altered.