4 Appendix
4.1 Technical Data
76
Electronic motor starter EMS-...-SWD
12/18 MN034002ZU-DE/EN
www.eaton.com
Ambient climatic conditions
Operating ambient temperature
°C
-5 - +60
-5 - +60
Condensation
not permissible -
prevent with suitable measures
not permissible -
prevent with suitable measures
Storage
°C
-40 - +80
-40 - +80
SmartWire-DT interface
Module type
SmartWire-DT module (slave)
SmartWire-DT module (slave)
Baud rate setting
automatic
automatic
Status display SmartWire-DT
LED
green/orange
green/orange
Connection
Plug, 8-pole,
Connector:
Blade terminal SWD4-8MF2
Plug, 8-pole,
Connector:
Blade terminal SWD4-8MF2
Supply voltage U
AUX
Rated operating voltage
V DC
24 (-15 % + 20 %)
24 (-15 % + 20 %)
Residual ripple of input voltage
%
≦
5
≦
5
Protection against polarity reversal
yes
yes
Current consumption
(if the +, EN+ / -, EN- inputs are linked)
mA
70
70
Supply voltage U
SWD
Rated operating voltage
V DC
15 (-30 % + 10 %)
15 (-30 % + 10 %)
Current consumption
mA
50
50
Potential isolation from U
AUX
yes
yes
Main circuit data
Operating voltage
V AC
42 - 500
42 - 500
Switching principle
Safety output stage with bypass,
3-phase switch off
Safety output stage with bypass,
3-phase switch off
Nominal rated frequency
Hz
45 - 65
45 - 65
Rated operational current I
e
(EN 60947-4-2)
AC51: EN 60947-4-3
A
0.18 - 2.4
1.5 - 9
AC53a: EN 60947-4-2
A
0.18 - 2.4
1.5 - 7
Break time for safe stop
normally
ms
30
30
maximum
ms
200
200
Break time in the event of a supply voltage loss
normally
ms
50
50
maximum
ms
500
500
Unit
EMS-…S-2.4-SWD
EMS-…S-9-SWD