4 Appendix
4.1 Technical Data
Electronic motor starter EMS-...-SWD
12/18 MN034002ZU-DE/EN
www.eaton.com
77
motor protection
Setting range
A
0.18 - 2.4
1.5 - 9
Minimum current for current measurement
A
0.15
1.2
Release class
Class 10
Class 10/10A
Pick-up time for 33 % current imbalance
s
120
120
Pick-up time for 67 % current imbalance
s
1.8
1.8
Stall protection threshold value
A
60
60
Stall protection response time
ms
500
500
Heat dissipation
electronic
W
2
2
Main circuits, minimum
W
0.1
1
Main circuits, maximum
W
2
12
Conformity/approval
EC prototype test certification according to ATEX
II (2) G [Ex d] [Ex px] [Ex e]
II (2) D [Ex t] [Ex p]
PTB 13 ATEX 3003
II (2) G [Ex d] [Ex px] [Ex e]
II (2) D [Ex t] [Ex p]
PTB 13 ATEX 3003
Unit
EMS-…S-2.4-SWD
EMS-…S-9-SWD