ELC DeviceNet (ELC-CODNET) Instruction Manual
May 2005
Pub. No.
MN0500300
5E
For more information visit: www.EatonElectrical.com
11
MAC ID setting for ELC-CODNET module
ELC-CODNET module has two rotary switches to set the
MAC ID in DeviceNet system. This is the only way for user
to set the MAC ID of ELC-CODNET module.
The MAC ID switches, allow user to set the address in a
decimal format.
ELC-CODNET module provide way that support user
update the firmware, so when the MAC ID switch is set to 95,
and re-power ELC-CODNET module, ELC-CODNET module will entry update mode.
Switch setting
Meaning
0 … 63
Valid DeviceNet MAC ID setting
95
Set module entry update mode
Other
Invalid DeviceNet MAC ID setting
Note:
Setting changes via address switches will not effective when ELC-CODNET is
operating. This means the setting changes will effective after ELC-CODNET power
re-boot or reset ELC-CODNET module.
Function switches setting
The function switch provides some combined function to
user, including baud rate setting, and hold or clear remote
control when loss network communication setting.
Note:
Setting changes via function switches will not effective when ELC-CODNET is operating.
This means the setting changes will effective after ELC-CODNET power re-boot or
reset ELC-CODNET module.
DR0-DR1 indicate the baud rate of unit in DeviceNet networks:
DR1
DR0
Baud rate
OFF OFF 125K
OFF ON 250K
ON OFF
500K
ON
ON
Auto Baud rate (not recommend)
5
4
3
2
1
0
9
8
7
6
3
2
1
4
0
5
9
6
7
8