Chapter 2
━
Specifications
Table 2-1: DeviceNet ELC-CODNET Specifications
Item
Specification
DeviceNet Connections
Interface
Pluggable connector (5.08mm)
Transfer method
CAN
Transfer cable
2-wire twisted shielded cable with 2-wrie bus power cable
and drain
Electrical isolation
500V DC
Communications
I/O Polling
Message types
Explicit
125 Kbaud
250 Kbaud
Baud Rates
500 Kbaud
Product Code
80
Product Type
12
Vendor ID
799
Electrical
Network supply voltage:
11 to 25V DC
Network input current:
28mA typical, 125 mA inrush (24V DC)
DeviceNet
All other power derived from ELC controller power supply
Environment
Ambient operating
temperature
-4-122
o
F (-10 to 50
o
C)
Storage temperature
-4-140
o
F (-20 to 60
o
C)
Humidity
<90%, no condensation allowed
Altitude
Max. 1000 meters
Vibration
0.5G 9-200 Hz
Safety
Fulfils EN50178 standard
Certification
CE, UL
CE Mark and UL Listed/Approved