7
Installation and operation manual for
conventional fire panels
EATON
www.eaton.com
Status Indications
Figure 5. Front panel status indications
This section shows the status indications on the front panel
(Figure 5) with a table to show the meaning .
Visual indications
Audible
Indications
Condition
P
ow
er O
N
G
ene
ral
F
aul
t
G
ene
ral
D
is
ab
le
R
ep
ea
te
r F
au
lt
/
S
ys
te
m
F
aul
t
B
at
te
ry F
au
lt
/
M
ai
ns
F
aul
t
B
at
te
ry
F
ailu
re
/
C
har
ge
r F
aul
t
S
oun
de
r F
aul
t/
S
ou
nd
er
D
is
ab
le
d
S
el
f T
est
O
n /
Test
FR
E O
n
FR
E F
au
lt
/
FR
E D
is
ab
le
d
FP
E F
au
lt
/
FP
E
D
is
ab
le
d
G
ene
ral
F
ire
Zo
ne F
ire (
1-
8)
D
et
ec
to
r R
em
ov
ed /
Zo
ne
Fa
ul
t/
Zo
ne
D
is
ab
le
d
Fi
re A
la
rm D
ev
ic
es
P
ane
l Bu
zz
er
Comments
Normal
Condition
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Normal condition and at access
level 1
Access Level
2 or 3
ON
FAST
Access level 2 or 3 pass code
accepted
Fire Condition
ON
ON
ON
ON
CONT CONT Only the zone in fire will have
its’ zone fire indicator lit
System Fault
ON
ON
ON
SLOW Severe fault condition with
the panel
Repeater Fault ON
ON
SLOW
SLOW Problem with the link between
panel and repeater
Battery Fault
ON
ON
SLOW
SLOW No battery voltage or battery
voltage too low
Mains Fault
ON
ON
ON
SLOW Mains voltage has been lost
Battery Failure ON
ON
SLOW
SLOW Battery impedance fault
Charger Fault
ON
ON
ON
SLOW Charger voltage fault
Sounder Fault
ON
ON
SLOW
SLOW Short or open circuit condition
on a zone
FRE Fault
ON
ON
SLOW
SLOW Short or open circuit condition
on a FRE
FPE Fault
ON
ON
SLOW
SLOW Short or open circuit condition
on a FPE
Zone Fault
ON
ON
SLOW
SLOW Short or open circuit condition
on the zone
Detector
removed
ON
ON
FAST
SLOW Detector removed on the zone
Sounder
disabled
ON
ON
ON
All fire alarm devices on all
zones disabled
FRE disabled
ON
ON
ON
FRE disabled
FPE disabled
ON
ON
ON
FPE disabled
Zone disabled
ON
ON
ON
Zone is disabled from fire
detection
Self test active ON
SLOW
SLOW The panel is in self test mode
Individual Zone
test active
ON
ON
ON
SLOW Individual zone is in test mode
and awaiting fire activation
Walk test
active
ON
ON
SLOW Panel is in walk test mode and
awaiting fire activation
KEY
ON
(---------)
Indicator lit
OFF
Indicator unlit
SLOW
( - - - - )
Indicator slow flashing, buzzer slow pulsing
FAST
( - - - - - )
Indicator fast flashing, buzzer fast pulsing
SILENT
Sounders off, buzzer off
CONT
Sounders on, buzzers continuous
Any condition could be indicated
Technical Data
25-16733-A
Effective
October 2019