21
Installation and operation manual for
conventional fire panels
EATON
www.eaton.com
Battery Fault Detection Check
Disconnect the battery .
After about 20 seconds check the following:
•
General fault indicator (amber) is on .
•
Battery/Mains fault indicator (amber) is flashing for battery fault .
•
Battery/Charger fault indicator (amber) is on for charger fault .
Connect the battery .
After about 4 seconds check the following:
•
General fault indicator is off .
•
Battery/Mains fault indicator is off .
•
Battery/Charger fault indicator is off .
Press the
Mute Buzzer
to silence the panel buzzer .
Zone Fire Detection Check
Repeat the following per zone:
•
Place the individual zone into Zone Test mode (see
Individual
Zone Test
on page 25) .
•
Activate a manual call point (or a detector if there is no call
point on the zone) in that zone and then check the following:
•
General fire indicator (red) is on .
•
Correct zone fire indicator (red) is on .
•
All fire alarm devices are sounding .
•
After approximately 3 seconds the system will automatically
silence and the fire indication will clear .
•
Take the zone out of Zone Test mode (see
Individual Zone
Test
) .
Reset the system to clear all fire indications .
Fire Outputs & Battery Check
WARNING
THIS TEST WILL ACTIVATE ANY EXTERNAL EQUIPMENT
CONNECTED TO THE FRE, FPE OR FIRE RELAYS. IF THE
ACTIVATION OF THE EQUIPMENT IS NOT DESIRED, THEN
THE EQUIPMENT MUST BE DISABLED, DISCONNECTED
OR POWERED OFF DURING THIS TEST AND RESTORED
ONCE THE TEST IS COMPLETE.
Measure the battery charger voltage, this should be around 27 .6V .
Disconnect the mains supply and check the following:
•
Power On (green) indicator is still on .
•
General fault (amber) indication is on .
•
Battery/Mains fault indication is on for mains fault .
The panel should not lose power during the following test .
Activate a call point in any zone .
Check the following on the panel:
•
General fire indicator (red) is on .
•
Correct zone fire indicator (red) is on .
•
FRE On indicator (red) is on .
•
FRE output has switched to 24V (if fitted) .
•
FPE output has switched to 24V (if fitted) .
•
Fire relay has switched over to C/NO .
•
All fire alarm devices are sounding .
Check the following on the interlinked panel (if installed):
•
General fire indicator (red) is on .
•
FRE On indicator (red) is on .
•
FRE output has switched to 24V (if fitted) .
•
FPE output has switched to 24V (if fitted) .
•
Fire relay has switched over to C/NO .
•
All fire alarm devices are sounding .
Perform a soft reset and then check that the panel and interlinked
panel have returned to the normal condition with mains fault .