Option Board Specification
EFCV2ZONE
EFCV4ZONE
EFCV8ZONE
Operating Voltage
18 .75-30 .7V DC
FRE Output
Rating
24V, 50mA
Fuse
50mA PTC
EOLR
6 .8KΩ
FPE Output
Rating
24V, 50mA
Fuse
50mA PTC
EOLR
6 .8KΩ
Number of Auxiliary Relays
2
4
8
Auxiliary Relays
(Un-monitored)
Type
Volt-Free, Single Pole Double Throw
Rating
30V DC, 50mA
Fuse
500mA PTC
Cable Specification
Recommended Cable size
1-1 .5mm2, Cable type - Firetuf FT120 /FP200
Manufacturer
Draka UK to Standard - suitable for all applications described in BS5839-1:2013, 6, 8 & 9 and BS5266-1
Technical Data
25-16733-A
Effective
October 2019