WIRING cont.
Flowmeter Input Wiring and DIP Switches
DIP Switch Position 3
1
3
2
4
Durant
®
X
+12 VDC Out
Flowmeter Input
Inhibit Input
Ground
Typical Flowmeter wiring (3
denotes terminal number)
4
3
1
DIP 1 ON
+
NPN
OUT
COMMON
4
3
1
DIP 1 OFF
+
PNP
OUT
COMMON
3
1
DIP 3 ON
2 Wire MAG Pickup
3
1
DIP 2 ON
Contact (Reed Switch, etc.)
The inhibit input (2
) is wired the same way, and DIP switches 1, 2, and 3 are set
accordingly.
Sensor Power Out
12 VDC, 75 mA max, short circuit protected
Dip Switch Settings
OFF
ON
#
Single Ended
Fast Response (>50 Hz)
Sourcing (PNP) Input
3
2
1
Mag Pickup
Slow Response (<50 Hz)
Sinking (NPN) Input
All manuals and user guides at all-guides.com