EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 47 of 107
ALARM CHANGE INDICATION
The time and date of the last alarm state change is shown in the
Alarms
menu on Web page and Display. The
last alarm change is also shown on the display Home page.
ALARM GROUPING
EC500 has provision for grouping of individual alarms. A maximum of 64 alarm groups can be configured. The
user can map individual alarm to up to two alarm groups. Grouping provides an OR function. User can edit
group names to match the requirement. Some of the group names may not be editable. Only Groups can be
mapped to operate output relays. Alarms cannot be mapped directly to relays. In case alarm grouping is not
required, users can map individual alarms to independent group.
If a Potential Free alarm output is required, the alarm should be mapped to at least one
alarm group.
Group Alarm Configurations
Parameter
Description
Where to find:
Number of Groups
Number of Groups available to user can be set.
Group Name
Group can be given a meaningful name to represent
the alarms grouped.
Refer section Digital Outputs on 59 for mapping Groups to Potential Free outputs.
SYSTEM ALARMS
These are generated by the operating values of dc power system (voltages, currents, temperatures etc.),
operation of power system modules (rectifiers, circuit breakers, fuses etc.) and communication alarms. The
EC500 system alarms are listed in Alarm Descriptions on page 97. The user can define alarm severity, Trap
operation and output mappings for System alarms. The user cannot change alarm names from Web page
though these can be changed in Configurator.
Configuration
The following system alarm parameters can be configured for individual system alarm.
Parameter
Description
Where to find:
Enable Alarm
If set to
Disabled
then the alarm will not activate.
Note that for some alarms enable / disable may not
be available.
These settings are available
under respective resource
settings e.g. alarm settings
for Battery will be available
under Battery Settings.
Display:
Menu>Settings>
xxx
Settings>Alarm Settings
Web:
Home>Settings>>
xxx
Settings>Alarm Settings
Alarm Severity
Alarm Severity (Critical / Major / Minor) of individual
alarm.
Enable Audible
Alarm Indication
Enable or disable the audible alarm indicator for
particular alarm.
Enable SNMP
If
Enabled,
SNMP Trap will be sent for this alarm. For
SNMPv3, alarm severity should be equal to or higher
than Trap receiver’s configured alarm severity.
See
page 86 for details.