10/10 MN05003003Z-EN
Outputs
13
Outputs
Table 2:
Type and number of outputs
The transistor outputs are provided with a short-circuit monitoring
function. In the event that a short-circuit occurs at one of the
outputs, this is indicated via the diagnostics inputs I15/I16. I15 is
set to 1 if a short-circuit occurs at the outputs Q1 to Q4. Input I16
is toggled if a short-circuit occurs on Q5 to Q6.
Memory card (MCC)
The memory card is used for data storage and supports the FAT16
file system.
Memory card data
On the memory card you can save the following data:
A brief description of the browser commands is provided from
page 59.
Data access on the memory card
Functions such as FileOpen or FileRead allow you to access the
files of the memory card from the user program. These functions
are provided in the library EC_File.lib and are described in the
Function Blocks manual (MN05010002Z-EN; previously
AWB2786-1456GB).
RUN/STOP/SF and CAN/NET LEDs
After power up, the CPU can switch to the following states, as
indicated by the LEDs:
Table 3:
LED status indicator
If the CPU is in RUN status, the CAN/NET LED indicates the
following states:
Table 4:
LED status signals for CAN/easyNet
EC4P-221/222-MT…
transistor outputs
8 (Q1…Q8)
24 V DC/0.5 A
EC4P-221/222-MR…
relay outputs
6 (Q1…Q6)
250 V AC/8 A
i
Caution!
Scan I15/I16 in the program. In the event of a short-circuit
set the outputs to 0 in order to prevent the thermal
overload of the output circuit.
Data
Transfer method
Boot project
Browser command: copyprojtommc
Startup.INI file
Browser command: createstartupini
Operating system (OS)
Updating the OS,
Source code of the
project
Online mode/Online menu: load source
code
General data
Online mode/Online menu:
Write file to PLC
Load file from PLC
h
Caution!
In order to avoid any loss of data, ensure that you have
closed all files of the program before removing / inserting
the memory card or switchingoff the power supply.
LED
Meaning/CPU status
RUN/STP/SF CAN/NET
red
red
1)
System test being run (up to 6 seconds after
start; after 6 seconds if no user program is
present).
CPU in NOT READY!
orange
orange
1)
System update in progress
red
off
1)
System test finished without error
red
flashing
red
flashing
1)
System test found a fault
orange
off
No user program present
CPU in NOT READY
green
flashing
–
Load user program
CPU in STOP
green
–
Load user program
CPU in RUN
red
–
Cycle time exceeded
CPU in STOP
orange
flashing
–
Continuous loop detected in program
CPU in STOP
red
flashing
red
flashing
Fatal error
1) LED is only relevant during startup/system test
LED
Meaning
RUN/STP/SF
CAN/NET
green
off
Communication not active
green
red
Bus status STOP
green
orange
Bus status PREOPERATIONAL
Station can be initialised, no transfer of
process data
green
green
Bus status OPERATIONAL
Process data transferred
Summary of Contents for easyControl EC4-200
Page 4: ...II...
Page 10: ...10 10 MN05003003Z EN 6...
Page 14: ...10 10 MN05003003Z EN 10...
Page 22: ...10 10 MN05003003Z EN 18...
Page 38: ...10 10 MN05003003Z EN 34...
Page 62: ...10 10 MN05003003Z EN 58...
Page 78: ...10 10 MN05003003Z EN 74...
Page 96: ...10 10 MN05003003Z EN 92...