2 Installation
2.5 Connecting inputs
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
33
2.5.1.2 Connect digital AC inputs to the expansion unit
Figure 13:
Connecting EASY…-AC-E digital inputs
Table 2:
easy-AB input signal values
Table 3:
easy-AC input signals
Voltage range of the input signals
Input current
OFF signal
ON signal
easy500/
easy700
I1 - I6
0 - 6 V AC
14 - 26.4 V AC
4 mA at 24 V AC
I7, I8
≧
7 V AC or
≧
9.5 V DC
2 mA with 24 V AC and 24 V DC
easy700
I9, I10
14 to 26.4 V AC
4 mA at 24 V AC
I11, I12
≧
7 V AC or
≧
9.5 V DC
2 mA with 24 V AC and 24 V DC
Voltage range of the input signals
Input current
OFF signal
ON signal
easy500/
easy700
I1 - I6
0 - 40 V
79 - 264 V
0.5 mA at 230 V AC/0.25 mA at
115 V AC
I7, I8
6 mA at 230 V AC/4 mA at 115 V
easy700
I9 - I12
0.5 mA at 230 V AC/0.25 mA at
115 V AC
easy600
R1 - R12
L
N
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
E+ E-
R11 R12
N
N
L
F1