11
Instruction leaflet
IL05407001E
Effective October 2010
E5-648-C446x electronic preset
counter with four presets (relays)
LCD negative, red-green backlighting
eaton corporation
www.eaton.com
Count mode ADDING with automatic
reset and Total counter
Output 2 (timed signal) active when
main counter = preset value 2
Automatic reset to zero when main
counter = preset value 2
Output 3 active when
main counter ≥ preset value 3
Total counter counts all the
count pulses from the main counter
Output 1 resp. 4 active when
total counter ≥ preset value 1 resp. 4
Manual Reset sets both counters to zero
Electronic reset only sets the main counter
to zero
7.8.6.3 Main menu for configuration
Main menu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting
determines the resolution
Unit of time: minutes
Decimal point setting
determines the resolution
Unit of time: hours
Decimal point setting
determines the resolution
Unit of time: hrs. min. sec.
Decimal point setting (Resolution)
Decimal place (determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value
Set value can be programmed
from 000000 to 999999.
A previously programmed
decimal point will be displayed
Display color (for device E5-648-C446x)
Display color
Upper line: red
Lower line: red
Display color
Upper line: red
Lower line: green
7.8.6.4 Main menu for reset mode
Setting the reset mode
Manual reset (with red key)
and electrical reset (reset input)
No reset possible
(red key and reset input inhibited)
Only electrical reset possible (reset input)
Only manual reset possible (red key)
7.8.6.5 Main menu for preset 1
Main menu for turning preset 1 ON/OFF
ADD mode output operations:
permanent signal at output 1,
becomes active when count ≥ preset 1
SUB mode output operations:
permanent signal at output 1,
becomes active when count ≤ preset 1
ADD mode output operations:
permanent signal at output 1,
becomes passive when count ≥ preset 1
SUB mode output operations:
permanent signal at output 1,
becomes passive when count ≤ preset 1
ADD mode output operations:
timed signal at output 1, becomes
active when count ≥ preset 1.
(Activation only in positive direction)
SUB mode output operations:
timed output at output 1, becomes
active when count ≤ preset 1
(Activation only in negative direction)
ADD mode output operations:
timed signal at output 1, becomes
passive when count ≥ preset 1.
(Deactivation only in positive direction)
SUB mode output operations:
timed output at output 1, becomes
passive when count ≤ preset 1.
(Deactivation only in negative direction)