background image

2

Instruction Leaflet 

IL29C119C

Effective August 2011

Installation Instructions for E2F, E2FM Mining Service Circuit Breakers

 

 

EATON CORPORATION

 www.eaton.com

 

WARNING

DO NOT ATTEMPT TO INSTALL, ADJUST, OR PER-
FORM MAINTENANCE ON EQUIPMENT WHILE IT IS
ENERGIZED. SEVERE PERSONAL INJURY, DEATH,

OR SUBSTANTIAL PROPERTY DAMAGE CAN

RESULT FROM CONTACT WITH ENERGIZED EQUIP-
MENT. ALWAYS VERIFY THAT NO VOLTAGE IS
PRESENT BEFORE PROCEEDING WITH THE TASK,

AND ALWAYS FOLLOW GENERALLY ACCEPTED
SAFETY PROCEDURES.

THE EATON CORPORATION IS NOT LIABLE

FOR THE MISAPPLICATION OR

 MISINSTALLATION OF ITS PRODUCTS.

The user is cautioned to observe all recommendations,
warnings, and cautions relating to the safety of personnel
and equipment, as well as, all general and local health

and safety laws, codes, and procedures.

The recommendations and information contained herein
are  based  on  Eaton  experience  and  judgement, but

should not be considered to be all-inclusive or covering
every application or circumstance which may arise. If

any questions arise, contact Eaton for further information

 or instructions.

1.0  INTRODUCTION

General Information

 E  F and E  FM mining service circuit breakers (Fig. 1-1) 

are  available  as  3-pole   devices,  in  several  ratings  from  3A
to 150A continuous current. The 

 are avail-

able in both thermal-magnetic and magnetic-only ver-
sions. Mining service circuit breakers have been
developed to meet the Federal Register ruling on trailing

 

2

 

cable  protection.

This instruction leaflet (IL) gives procedures for the instal-

lation and field testing of E  F and E  FM  mining service

circuit  breakers.  For  this  publication,  mining  service 
circuit breaker shall be abbreviated to circuit breaker.

Fig. 1-1 

 E  F Magnetic ONLY Mining Service Circuit

Breaker

2.0  INSTALLATION

The installation procedure consists of inspecting and

mounting the circuit breaker, connecting and torquing the
line and load terminations, and attaching terminal shields
or barriers (when supplied). To install the circuit breaker,
perform  the  following  steps:

Note: The 

 

2

 

 E  F and E  FM circuit breakers are factory

sealed. Where local codes and standards permit,

internal accessories can be field installed. Accessory
installation should be done before the circuit breaker
is mounted and connected.

Mounting hardware and unmounted terminations
(where required) are supplied in separate packages.

2.1.

Make sure that the circuit breaker is suitable for the
intended installation by comparing nameplate data
with system requirements. Inspect the circuit
breaker  for  completeness,  and  check  for  damage
before  mounting.

 

 

2

 

 

2

 

 

2

 

 

2

 

E  F and E  FM

 

2

 

 

2

 

 

2

 

 

2

 

Summary of Contents for E2F

Page 1: ...ion 2 2 0 Installation 2 3 0 Manual Operation 4 4 0 Inspection and Field Testing 5 Effective August 2011 Supersedes IL 29C119B Dated 10 01 Instruction Leaflet IL29C119C Installation Instructions for E2 F E2 FM Mining Service Circuit Breakers ...

Page 2: ...ole devices in several ratings from 3A to 150A continuous current The are avail able in both thermal magnetic and magnetic only ver sions Mining service circuit breakers have been developed to meet the Federal Register ruling on trailing 2 cable protection This instruction leaflet IL gives procedures for the instal lation and field testing of E F and E FM mining service circuit breakers For this p...

Page 3: ...t mounting panel is predrilled using bolt drilling plan Fig 2 1 For panelboard mounting only load end support mounting holes are required For deadfront cover applications make sure mounting panel cover is cut out to correct escutcheon dimensions Fig 2 2 b If circuit breaker includes factory installed inter nal accessories make sure accessory wiring can be reached when the circuit breaker is mounte...

Page 4: ...Supplied 1O 32 35 4 0 Slotted 1O 32 35 4 0 3 0 MANUAL OPERATION Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP but ton The circuit breaker handle has three indicated posi tions two of which are shown on the cover with raised lettering to indicate ON and OFF On the sliding handle barrier ON OFF and trip are also shown by a color coded strip ...

Page 5: ...nical linkages are free and do not bind If mechanical linkages are not free replace circuit breaker Press the PUSH TO TRIP button to mechanically trip the circuit breaker Trip reset and switch circuit breaker ON several times If mechanism does not reset each time the circuit breaker is tripped replace the circuit breaker Check base cover and operating handle for cracks chipping and discoloration C...

Page 6: ...tting Number Setting A 0 0 5 A 0 9 B 12 0 B 60 0 C 15 0 C 75 0 D 3 18 0 D 30 90 0 E 21 0 E 105 0 F 24 0 F 120 0 G 27 0 G 135 0 H 30 0 H 150 0 A 21 0 0 9 A B 28 0 B 120 0 C 35 0 C 150 0 D 7 42 0 D 30 180 0 E 49 0 E 210 0 F 56 0 F 240 0 G 63 0 G 270 0 H 70 0 H 300 0 A 0 6 6 A 0 5 4 B 60 0 B 97 0 C 75 0 C 112 5 D 15 90 0 D 50 128 0 E 105 0 E 143 5 F 120 0 F 159 0 G 135 0 G 174 5 H 150 0 H 190 0 A 40 ...

Page 7: ...0MM 490 0 F 560 0 G 630 0 H 700 0 0 0 5 1 A B 200 0 C 250 0 D 100 E2Fl OOKM 300 0 E E2FMl OOKM 350 0 F 420 0 G 450 0 H 500 0 0 0 0 3 A B 400 0 C 500 0 D 100 E2Fl OORM 600 0 E E2FMlOORM 700 0 F 800 0 G 900 0 H 1000 0 0 0 5 4 A B 600 0 C 750 0 D 150 EZFI 50TM 900 0 E EZFM150TM 1050 0 F 1200 0 G 1350 0 H 1500 0 TABLE 3 1 MCP TRIP SETTINGS CONT Cam Continuous MCP MCP Setting Amps Catalog Trip Number S...

Page 8: ... consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equi...

Reviews: