background image

3

Instruction Leaflet 

IL29C119C

Effective August 2011

Installation Instructions for E2F, E2FM Mining Service Circuit Breakers

 

 

EATON CORPORATION

 www.eaton.com

WARNING

BEFORE MOUNTING THE CIRCUIT BREAKER IN AN

ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT

BREAKER IS SWITCHED TO THE OFFPOSITION

AND THAT THERE IS NO VOLTAGE PRESENT

WHERE WORK IS TO BE PERFORMED. SPECIAL

ATTENTION SHOULD BE PAID TO REVERSE FEED

APPLICATIONS TO ENSURE NO VOLTAGE IS

PRESENT. THE VOLTAGES IN ENERGIZED EQUIP-

MENT CAN CAUSE SEVERE PERSONAL INJURY OR

DEATH.

2.2. Depending on the equipment configuration, the cir-

cuit breaker can be mounted using different styles

of hardware. The following steps describe how to

mount the circuit breaker using standard hardware.

When special hardware is needed (for example,

with the electrical operator), the instruction leaflet

describing the accessory also describes the special

mounting  arrangements.

Note: Before mounting the circuit breaker, check if

the termination devices should be installed first. See

instructions supplied with terminations.

2.3. To  mount  the  circuit  breaker,  perform  the  following

steps.

a. For individual mounting panels, make sure that

mounting panel is predrilled using bolt drilling

plan (Fig. 2-1). For panelboard mounting, only

load end support mounting holes are required.

For deadfront cover applications, make sure

mounting panel cover is cut out to correct

escutcheon dimensions (Fig. 2-2).

b. If circuit breaker includes factory installed inter-

nal accessories, make sure accessory wiring

can be reached when the circuit breaker is

mounted.

c. Position circuit breaker on mounting surface.

d. Install mounting screws, washers, and nuts.

Tighten screws firmly, but do not exceed 28

pound-inches  (3.16  N.m.).

2.4. If an optional terminal end cover is to be installed

with the circuit breaker (usually line-end only), it

must be positioned before cables are connected to

terminals.

Fig. 2-1  Circuit Breaker Mounting Bolt Drilling Plan

Circuit  Breaker

Handle

33.66

Access  to  Push-to-Trip

  (6.35)  Dia.  Hole  for

Access  to  Pickup  Adjustment

Button  (Magnetic  only}

Fig. 2-2. Circuit Breaker Escutcheon Dimensions

CAUTION

WHEN ALUMINUM CONDUCTORS ARE USED, THE

APPLICATION OF A SUITABLE JOINT COMPOUND

IS RECOMMENDED TO REDUCE THE POSSIBILITY

OF TERMINAL OVERHEATING. TERMINAL OVER-

HEATING CAN CAUSE NUISANCE TRIPPING AND

DAMAGE TO THE CIRCUIT BREAKER.

2.5. After mounting the circuit breaker, line and load ter-

minals and accessory leads should be connected.

Handle

Circuit Breaker

Load End

Line End

Circuit Breaker

Handle

Summary of Contents for E2F

Page 1: ...ion 2 2 0 Installation 2 3 0 Manual Operation 4 4 0 Inspection and Field Testing 5 Effective August 2011 Supersedes IL 29C119B Dated 10 01 Instruction Leaflet IL29C119C Installation Instructions for E2 F E2 FM Mining Service Circuit Breakers ...

Page 2: ...ole devices in several ratings from 3A to 150A continuous current The are avail able in both thermal magnetic and magnetic only ver sions Mining service circuit breakers have been developed to meet the Federal Register ruling on trailing 2 cable protection This instruction leaflet IL gives procedures for the instal lation and field testing of E F and E FM mining service circuit breakers For this p...

Page 3: ...t mounting panel is predrilled using bolt drilling plan Fig 2 1 For panelboard mounting only load end support mounting holes are required For deadfront cover applications make sure mounting panel cover is cut out to correct escutcheon dimensions Fig 2 2 b If circuit breaker includes factory installed inter nal accessories make sure accessory wiring can be reached when the circuit breaker is mounte...

Page 4: ...Supplied 1O 32 35 4 0 Slotted 1O 32 35 4 0 3 0 MANUAL OPERATION Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP but ton The circuit breaker handle has three indicated posi tions two of which are shown on the cover with raised lettering to indicate ON and OFF On the sliding handle barrier ON OFF and trip are also shown by a color coded strip ...

Page 5: ...nical linkages are free and do not bind If mechanical linkages are not free replace circuit breaker Press the PUSH TO TRIP button to mechanically trip the circuit breaker Trip reset and switch circuit breaker ON several times If mechanism does not reset each time the circuit breaker is tripped replace the circuit breaker Check base cover and operating handle for cracks chipping and discoloration C...

Page 6: ...tting Number Setting A 0 0 5 A 0 9 B 12 0 B 60 0 C 15 0 C 75 0 D 3 18 0 D 30 90 0 E 21 0 E 105 0 F 24 0 F 120 0 G 27 0 G 135 0 H 30 0 H 150 0 A 21 0 0 9 A B 28 0 B 120 0 C 35 0 C 150 0 D 7 42 0 D 30 180 0 E 49 0 E 210 0 F 56 0 F 240 0 G 63 0 G 270 0 H 70 0 H 300 0 A 0 6 6 A 0 5 4 B 60 0 B 97 0 C 75 0 C 112 5 D 15 90 0 D 50 128 0 E 105 0 E 143 5 F 120 0 F 159 0 G 135 0 G 174 5 H 150 0 H 190 0 A 40 ...

Page 7: ...0MM 490 0 F 560 0 G 630 0 H 700 0 0 0 5 1 A B 200 0 C 250 0 D 100 E2Fl OOKM 300 0 E E2FMl OOKM 350 0 F 420 0 G 450 0 H 500 0 0 0 0 3 A B 400 0 C 500 0 D 100 E2Fl OORM 600 0 E E2FMlOORM 700 0 F 800 0 G 900 0 H 1000 0 0 0 5 4 A B 600 0 C 750 0 D 150 EZFI 50TM 900 0 E EZFM150TM 1050 0 F 1200 0 G 1350 0 H 1500 0 TABLE 3 1 MCP TRIP SETTINGS CONT Cam Continuous MCP MCP Setting Amps Catalog Trip Number S...

Page 8: ... consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equi...

Reviews: